[. . . ] Switch Mode Power Supply
S8TS
Block-type Switch mode Power Supply That Mounts to DIN Track
· Power supply range of 60 to 240 W available with just one model (24-V models). · Easy creation of multi-power supply configurations with different output power supplies connected together (24-V, 12-V, and 5-V models). · Improve power supply system reliability by creating N+1 redundant systems (24-V and 12-V models). · Approved by UL/CSA standards, EN60950 (IEC 950), and VDE 0160.
Model Number Structure
Model Number Legend
S8TS- [. . . ] Power Supplies Item Value Definition
Life expectancy
10 yrs min.
Switch Mode Power Supply
S8TS
L-27
Connections
Block Diagrams
S8TS-06024@ and S8TS-03012@
AC (L) INPUT AC (N)
Fuse 2. 0 A Noise filter
+V DC OUTPUT
Rectifier
Inrush current protection circuit Harmonic current suppression circuit Smoothing circuit
Rectifier and smoothing circuit
Protection diode
-V
DC LOW OUT
Drive control circuit
Current detection circuit
Undervoltage indicator/output
Ocercurrent detection circuit
Detection circuit
Ocervoltage detection circuit
Photocoupler
Connected to Bus Line Connector
Connected to Bus Line Connector
S8TS-02505@
AC(L) INPUT AC(N)
Fuse 2. 0 A Noise filter
+V DC OUTPUT
Rectifier Inrush
Harmonic current suppression circuit Smoothing circuit
current protection circuit
Rectifier and smoothing circuit
-V
DC LOW OUT
Drive control circuit Undervoltage indicator/output
Overcurrent detection circuit
Detection circuit
Overvoltage detection circuit
Photocoupler
Connected to Bus Line Connector
Connected to Bus Line Connector
L-28
Switch Mode Power Supply S8TS
Installation
Basic Blocks with Screw Terminals: S8TS-@
123
10
Basic Blocks with Connector Terminals: S8TS-@F
1 2 3
10
L INPUT
50/60Hz AC100 -240V 1. 0A
N
L INPUT
50/60Hz AC100 -240V 1. 0A
N
L
L N
N
S8TS-06024
POWER SUPPLY
-V +V
S8TS-06024F
POWER SUPPLY -V
+V
DC ON
7 8 9
DC LOW V. ADJ -V
Class2 Power Supply
OUTPUT
DC24V 2. 5A +V
7 8 9
DC ON DC LOW V. ADJ -V
Class2 Power Supply
OUTPUT
DC24V 2. 5A +V
DC LOW
DC LOW
456
10
456
10
A AC Input Terminal (L): Connect an input line to this terminal. B AC Input Terminal (N): Connect an input line to this terminal. C Ground Terminal ( ): Connect a ground line to this terminal. D Undervoltage Detection Output (DC LOW OUT): Open Collector output E DC Output Terminal (V): Connect load lines to this terminal. F DC Output Terminal (+V): Connect load lines to this terminal. G Output Indicator (DC ON: Green): Lights while DC output is ON. H Undervoltage Indicator (DC LOW: Red): Lights when the voltage at the output terminal drops. I Output Voltage Adjuster (V. ADJ): Use to adjust the voltage. J Slider: Slide to the lock side when connecting. Unlock the slider when disconnecting.
S8T-BUS01 Bus Line Connector (AC Line + DC Line Bus)
S8T-BUS02 Bus Line Connector (AC Line Bus)
1 2
1 2
7 3 4 5 6
8
8 3
A AC Input Terminal (L) B AC Input Terminal (N) C Ground Terminal ( ) D Parallel Operation Signal Terminal E DC Output Terminal (+V) F DC Output Terminal (-V) H Projected Indicator Section Power Supplies G Selector
Switch Mode Power Supply
S8TS
L-29
Operation
Maximum Number of Blocks That Can Be Linked
Basic Blocks can be linked using Bus Line Connectors.
Mounting and Removing Bus Line Connectors
Pay attention to the following points to maintain electrical characteristics. · Do not insert/remove the Connectors more than 20 times. · Do not touch the Connector terminals. When N Blocks are linked together, the inrush current will be equal to N times that for 1 Basic Block. Be sure to use a fuse with the appropriate fusing characteristics or a breaker with the appropriate tripping characteristics.
5-V models
L N
Leakage Current
S8T -BUS02 S8T -BUS02
The leakage current per Basic Block is 0. 35 mA at 100 VAC and 0. 7 mA at 240 VAC. When N Blocks are linked together, the leakage current will be equal to N times that for 1 Basic Block.
Load Load
Load
Load
Load
Load
Adjusting Output Voltage for Parallel Operation
The Blocks are factory-set to the rated output voltage. When adjusting voltages, set the same values for Blocks with V. ADJ before linking them together. Adjust the set values within the limits given in the following table. Model number S8TS-06024@ S8TS-03012@ Difference between output voltages 0. 24 V max. 0. 12 V max.
Mounting
Mounting Direction
Standard mounting Face-up mounting Other mounting methods Yes No No
Use standard mounting only. Using any other mounting method will prevent proper hear dissipation and may result in deterioration or damage of internal elements.
Standard mounting
Face-up mounting
Do not adjust voltages after Blocks are linked together. [. . . ] Do not touch the Power Supply while power is supplied or immediately after power is turned OFF. The Power Supply becomes hot and touching it may result in injury.
Recommended Wire Size for Parallel Operation
Model S8TS-06024 S8TS-03012 Recommended wire size For 2 Units con- AWG 14 to 18 (cross-sectional arnected in paral- ea: 0. 823 to 2. 081 mm2) lel For 3 Units con- AWG 14 to 16 (cross-sectional arnected in paral- ea: 1. 309 to 2. 081 mm2) lel For 4 Units con- AWG 14 (cross-sectional area: nected in paral- 2. 081 mm2) lel S8TS-06024F S8TS-03012F For 2 Units con- AWG 12 to 18 (cross-sectional arnected in paral- ea: 0. 823 to 3. 309 mm2) lel For 3 Units con- AWG 12 to 16 (cross-sectional arnected in paral- ea: 1. 309 to 3. 309 mm2) lel For 4 Units con- AWG 12 to 14 (cross-sectional arnected in paral- ea: 2. 081 to 3. 309 mm2) lel
Mounting
To improve the long-term reliability of devices, give due consideration to heat dissipation when mounting. With the S8TS, heat is dissipated by natural convection. Mount Blocks in a way that allows convection in the atmosphere around them.
*1 *1 *2
*1 *4
*1
*3
*1. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON S8TS
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.