Manual abstract: user guide OMRON VARISPEED J7DATASHEET
Detailed instructions for use are in the User's Guide.
[. . . ] with potentiometer 3G3IV-PEZZ8122_ DIN attachment
Line filter
3G3IV-PCN329-E Inverter to PC cable
3G3IV-PCN126/326 Digital operator extension cable
Varispeed J7
Varispeed J7
351
Specifications
Type designation
CIMR--J7AZ20P1
Inverter J7 series
A: With digital operator (with potentiometer)
Max. applicable motor output 0P1: 0. 1 kW 4P0: 4. 0 kW
[
~
"P" indicates a decimal point
]
Z: European standard specifications
Voltage B: Single-phase 200 VAC 2: Three-phase 200 VAC 4: Three-phase 400 VAC
Voltage class Model CIMR-J7AZ# Three-phase Single-phase1 20P1 B0P1 0. 12 0. 3 0. 8 20P2 B0P2 0. 25 0. 6 1. 6
200 V single/three-phase 20P4 B0P4 0. 55 1. 1 3 20P7 B0P7 1. 1 1. 9 5 21P5 B1P5 1. 5 3. 0 8 22P2 2. 2 4. 2 11 24P0 4. 0 6. 7 17. 5 40P2 0. 37 0. 9 1. 2 40P4 0. 55 1. 4 1. 8
400 V three-phase 40P7 1. 1 2. 6 3. 4 41P5 1. 5 3. 7 4. 8 42P2 2. 2 4. 2 5. 5 43P0 3. 0 5. 5 7. 2 44P0 4. 0 7. 0 9. 2
Max. applicable motor output kW (HP)2 Output characteristics Inverter capacity kVA Rated output current A Max. [. . . ] 0. 5 s or shorter, continuous operation Protected by thermister Individual level stall prevention can be set during acceleration or constant running, provided/not provided setting available during deceleration. Detected by electronic circuit (fan lock detection) Protected by electronic circuit (operation level is approx. 250% of rated output current) ON until the DC bus voltage becomes 50 V or less, RUN lamp stays ON or digital operator LED stays ON. (Charge LED is provided for 400 V) IP20 Self cooling for 200 V 0, 1. . 0, 75 kW (single-phase) 0, 1. . 0, 4 kW (Three-phase) and for 400 V 0, 2. . 0, 75l kW Cooling fan for 200 V (single-phase), 0. 75 kW. . 4. 0 kW (3-phase) and for 400 V 1, 5. . 4. 0 kW -10 ºC to 50 ºC (non-freezing) 90% RH or less (non-condensing) -20 ºC. . +60 ºC (short-term temperature during trasnportation) Indoor (no corrosive gas, dust, etc. ) Max. 1000 m 10 to 20 Hz, 9. 8 m/s2 max; 20 to 50 Hz, 2m/s2 max
Control functions Functionality
V/f characteristics Digital inputs
Digital outputs
Standard functions
Display
Shows deceleration torque for uncoupled motor decelerating from 60 Hz with the shortest possible deceleration time.
Varispeed J7
353
Digital operator
Digital operator
Function display LEDs Data display
Selected function is lit (see the functions below). Its data is displayed on data display.
Display selection key
Switch functions among function display LEDs.
Operation key
Press to run the motor. The RUN light is ON while running.
Enter key
Enter data when setting constants. at PRGM mode, data are displayed.
Alarm LED
Run LED
Increment key
Increase constant no. or data.
Frequency setting volume
Set operational frequency with volume.
Decrement key
Decrease constant no. or data.
Stop/Reset key
Press to stop the motor. If fault occurs, reset the inverter.
FREF
FOUT
IOUT
Output current monitoring
MNTR
Multi-function monitoring
Frequency reference Output frequency setting/monitoring monitoring
F/R
Operator RUN command FWD/REV selection
LO / RE
LOCAL/REMOTE selection
PRGM
Constant no. /data
354
Frequency inverters
Dimensions
IP 20 type 0. 1 to 4 kW
4M4 2M4
8. 5 (0. 34)
8. 5 (0. 34)
Figure 1
Figure 2
Voltage class
Max. applicable motor output kW 0. 12 0. 25 0. 55
Inverter model CIMR-J7AZ# 20P1 20P2 20P4 20P7 21P5 22P2 24P0 B0P1 B0P2 B0P4 B0P7 B1P5 40P2 40P4 40P7 41P5 42P2 43P0 44P0
Figure 1
Dimensions in mm W 68 H 128 D 70 102 122 W1 56 H1 118 H2 5
Weight kg 0. 5 7. 7 0. 8 0. 9
Cooling method Self cooled
200 V three-phase
1. 1 1. 5 2. 2 4. 0 0. 1 0. 2
Fan cooled
2
108 140
129 154 161 128 70 112
96 128 56
118
1. 3 1. 5 2. 1
1
68
118
5
0. 5 0. 9
Self cooled
200 V single-phase
0. 4 0. 75 1. 5 0. 37 0. 55 1. 1
2 2
108 108 128
129 154 81 99 129 154
96 96 118 5
1. 5 1. 0 1. 1 1. 5
Fan cooled Self cooled
400 V three-phase
1. 5 2. 2 3. 0 4. 0
Fan cooled 140 161 128 2. 1
Varispeed J7
355
Filters
Schaffner model 3x200 V 1x200 V 3x400 V 3G3JV-PFI2010-SE 3G3JV-PFI2020-SE 3G3JV-PFI1010-SE 3G3JV-PFI1020-SE 3G3JV-PFI3005-SE 3G3JV-PFI3010-SE 3G3JV-PFI3020-SE
Dimensions A 194 169 169 169 169 169 174 B 82 111 71 111 111 111 144 C 50 50 45 50 50 50 50 D 160 135 135 135 135 135 135 E 181 156 156 156 156 156 61 F 62 91 51 91 91 91 120 G 5. 3 5. 5 5. 3 5. 3 5. 3 5. 3 5 H M5 M5 M5 M5 M5 M5 M5 I 25 25 22 25 22 22 28 J 56 96 56 96 96 96 128 K 118 118 118 118 118 118 118 L M4 M4 M4 M4 M4 M4 M4
Drive mounts
Output flexes
Rasmi model 3x200 V 3G3JV-PFI2010-E 3G3JV-PF2020-E 3G3JV-PFI2030-E 1x200 V 3x400 V 3G3JV-PFI1010-E 3G3JV-PFI1020-E 3G3JV-PFI3005-E 3G3JV-PFI3010-E 3G3JV-PFI3020-E
Dimensions W 82 111 144 71 111 111 111 144 H 50 50 50 45 50 50 50 50 L 194 169 174 169 169 169 169 174 X 181 156 161 156 156 156 156 161 Y 62 91 120 51 91 91 91 120 Inverter fixing M5 M5 M5 M5 M5 M5 M5 M5
356
Frequency inverters
DIN rail mounting bracket
3G3IV-PEZZ08122A
3G3IV-PEZZ08122B
(35 . 1) DIN rail
. 1) (35
Four, M4 tap
Four, M4 tap
3G3IV-PEZZ08122C
Four, M4 tap
3-phase 200 VAC
Single-phase 200 VAC 3-phase 400 VAC
Inverter CIMR-J7AZ20P1/20P2/20P4/20P7 CIMR-J7AZ21P5/22P2 CIMR-J7AZ24P0 CIMR-J7AZB0P1/B0P2/B0P4 CIMR-J7AZB0P7/B1P5 CIMR-J7AZ40P2/40P4/40P7/41P5/42P2 CIMR-J7AZ43P0/44P0
DIN rail mounting bracket 3G3IV-PEZZ08122A 3G3IV-PEZZ08122B 3G3IV-PEZZ08122C 3G3IV-PEZZ08122A 3G3IV-PEZZ08122B 3G3IV-PEZZ08122B 3G3IV-PEZZ08122C
Varispeed J7
DIN
rail
357
Installation
Standard connections
U
DC reactor (option) short X bar
+2 R/L1 S/L2 T/L3 U/T1 V/T2 +1 -
MCCB R S T
Forward run/stop Reverse run/stop Multifunction input Fault reset External fault (no contact) Multi-step speed reference 1
Varispeed J7AZ
S1 S2 S3
IM
W/T3
Grounding
MA
S4 S5 SC
MB Running MC
Multi-function output 250 VAC 1 A or less 30 VDC 1 A or less
Shield connection terminal Pulse train input Frequency reference
FS supply (+12 V 20 mA) P P
Frequency setting power Speed frequency reference Speed reference
2 k
Frequency setter
FR 0 To 10 V (20 k ) or 4 to 20mA (250 ) pulse train (33 kHz max. ) FC or O to 20 mA (250 ) 0V
Digital operator frequency setting min max volume
AM AC indicates shielded wire. : shows the connection for the following two kinds of sequence input (S1 to S5) signals: no-voltage contact and NPN transistors (0 V common). For a PNP transistor (+24 V common), a 24 V external power supply is necessary.
Frequency meter adjusting potentiometer Analog monitor P FM output Output frequency
0 To 10 VDC (2 mA)
358
Frequency inverters
Main circuit
Terminal R/L1, S/L2, T/L3 U/T1, V/T2, W/T3 +2, +1 +1, Name AC power supply input Inverter output DC reactor connection DC power supply input Grounding Function (signal level) Main circuit power supply input (Use R/L1 and S/L2 for single-phase power supply inverter. [. . . ] MTG holes
80 (3. 15)
50 (1. 97)
DSPL
DATA ENTER
RUN
MIN MAX
STOP RESET
Remote digital operator with potentiometer
78 (3. 07) 88 (3. 46)
5 (0. 2)
1. 7 (0. 07) 12. 2 (0. 48) 9. 3 (0. 37)
10. 5 (0. 41)
56 (2. 20) 4-M4 spot facing deep 3. 5 (0. 14)
23. 1 (0. 91)
18. 2 30. 4 (0. 72) (1. 20)
15. 5 (0. 61)
Varispeed J7
68 (2. 68)
68 (2. 68)
363
Type
Model SI-232/J7 (3G3JV-PSI232J)
Description
Funtions Another option SI-232/J7C (3G3JV-PSI232JC) is available, the only difference is that this one is removable.
21. 5 (0. 85)
RS232 adapter
15. 5 (0. 61)
63(2. 48)
29 (1. 14)
2. 5 19 (0. 1) (0. 75)
8(0. 31
Interface units
SI-485/J7 (3G3JV-PSI485J)
16 (0. 63)
12 (0. 47)
4 3. 8(0. 15)=15. 2(0. 6)
13(0. 51)
RS485 adapter
63 (2. 48)
29 (1. 14)
8 19 8 (0. 3) (0. 75) (0. 3)
Accessories
3G3IV-PCN126 3G3IV-PCN326 3G3IV-PCN329-E
Digital operator extension cable SI232/J7 must be connected 1 meter 3 meters PC configuration cable SI232/J7 must be connected
B Accessories
Type Software Model CX-drive CX-One Description Computer software Computer software Installation Configuration and monitoring software tool for drives. Complete OMRON automation software including CX-drive.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0. 03937. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON VARISPEED J7
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual OMRON VARISPEED J7 will begin.