[. . . ] N138-E1-01
WT30
FA Wireless SS Terminal
Notice (1) This manual may not be copied, reproduced, or reprinted, in whole or in part, without permission from OMRON. (2) The specifications listed within this manual may be revised without prior notice. (3) The information in this manual was compiled with the utmost care. However, if you should find any errors or inconsistencies, please contact the OMRON business office. [. . . ] Received Signal Strength Indicator
Red indicators Field strength Number of indicators lit RUN mode TEST mode Field strength monitor test
Installation/confirmation test
Weak
0
1
Unstable communications range
Range in which specified channel can be used.
Unstable communications range
The received signal strength is indicated using 10 levels. Check the communications status, referring to the field strength level.
42
456
456
X1
Yellow indicators Medium
Green indicators Strong
2
3
4
5
6
7
8
9
Stable communications range
Range in which specified channel cannot be used. Stable communications range
Using Unregistered Communications Partners
Section 3-4
3-4-2
Operation Settings
1, 2, 3. . . Before turning ON the power, set the function setting switch as required.
ON 12345678 90
Bit 1: Hold/clear I/O data if communications errors occur Bit 2: Input hold/normal mode Bit 3: Input filter (100 ms/10 ms)
I/O Slave Station Settings
2. Set the node number of the I/O Slave Station using the node setting switch.
W NODE
901
78
23
901
Setting range: 01 to 64
78
456
23
X10
3. Set the same frequency channel used by the Serial Master Station using the channel setting switch.
78
78
X10
4. Change the setting for the mode setting switch to RUN mode, and then turn ON the power.
RUN TEST SET
Serial Master Station Settings 1, 2, 3. . . Before turning ON the power set the function setting switch as required.
ON 12345678 90
Bit 1: Hold/clear I/O data if communications errors occur Bit 2: OFF (scan list disabled)
Note
When the scan list is disabled, communications are performed with the number of I/O Slave Stations set using the node setting switch. Example 1: If the node setting switch is set to 2, communications will be performed with up to 02 I/O Slave Stations. Example 2: If the node setting switch is set to 64, communications will be performed with up to 64 I/O Slave Stations. Set the number of I/O Slave Stations to be connected using the node setting switch. Polling will be performed for the number of I/O Slave Stations set here. For example, if the number is set to 2, communications will be performed with only 2 Stations even if 3 or more Stations actually exist.
W NODE
901
901
Setting range: 01 to 64
78
78
X10
456
456
456
X1
W CH
901 901
23
Setting range: 01 to 34, 51 to 83
23
23
456
456
X1
X1
23
43
Using Unregistered Communications Partners
Section 3-4
3. Set the frequency channel using the channel setting switch.
W CH
901 901
Setting range: 01 to 34, 51 to 83
78
78
456
23
23
X10
4. Change the setting for the mode setting switch to RUN mode, and then turn ON the power.
3-4-3
Confirming Connection Status
Confirm the communications status between the I/O Slave Stations and Serial Master Station using the RSSI (received signal strength indicator) display. To confirm the status from the Serial Master Station, specify the I/O Slave Station to be monitored using the node setting switch. Be sure to turn ON the power to the I/O Slave Station in RUN mode before the Serial Master Station.
I/O Slave Stations 1, 2, 3. . . Confirm that the mode setting switch on the I/O Slave Station is set to RUN mode.
2. Confirm that the MS and WS indicators on the I/O Slave Station are lit green.
MS: Module status indicator WS: Wireless status indicator
MS
3. Check the strength of the received signal from the Serial Master Station indicated using 10 levels on the RSSI display.
Number of LEDs lit: Field strength: Few Weak Many Strong
Serial Master Station 1, 2, 3. . . Confirm that the mode setting switch on the Serial Master Station is set to RUN mode.
44
456
X1
RUN TEST SET
RUN TEST SET
WS
RUN TEST SET
Registering the Communications Partner
Section 3-5
2. Confirm that the MS and WS indicators on the Serial Master Station are lit green.
MS: Module status indicator WS: Wireless status indicator
MS
WS
3. [. . . ] = WNODE (Sum total of cycle times for all I/O Slave Stations) = WNODE (10 ms × n stations) Using Relay Stations The wireless communications delay is doubled when a Relay Station is used. = WNODE (10 ms × n stations × 2) Example 1: Using one Master Station, four I/O Slave Stations, and an input filter of 10 ms. 10 × 4 × 2 + 10 = 90 ms Example 2: Using one Master Station, one Relay Station, four I/O Slave Stations, and an input filter of 10 ms. 10 × 4 × 2 × 2 + 10 = 170 ms The calculations shown here indicate theoretical values and should be considered as a rough guide only. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON WT30
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.