[. . . ] The switching differential is 1 K.
3031D01
Q14
ON
T SD W Q14
Room temperature Switching differential Room temperature setpoint Output signal for heating
OFF
W SD
T[°C]
Operating modes The RDD10. . . provides normal operation and, optionally, energy saving mode or OFF. [. . . ] When the function "automatic operating mode change over" is activated, the hour glass symbol is shown.
When this function is activated and a manual changeover has been made, the operating mode will automatically be reset on completion of an adjustable period of time. This
Display
Display in normal operation
Display in energy saving mode
2/8 Siemens Building Technologies HVAC Products Room temperature controllers CE1N3031en 24. 09. 2003
Type summary Type reference RDD10 RDD10. 1 Features Mains-powered AC 230 V Battery-powered DC 3 V
Ordering When ordering, please give name and type references, e. g. Valve actuators are to be ordered as separate items.
Equipment combinations Type of unit Motoric on/off actuator Thermal actuator (for radiator valve) Thermal actuator (for small valve 2, 5 mm) Accessories Type reference SFA21. . . .
Description Adapter plate 120 x 120 mm for 4" x 4" conduit boxes Adapter plate 96 x 120 mm for 2" x 4" conduit boxes Adapter plate for surface wiring 112x130 mm Mechanical design
Type reference ARG70 ARG70. 1 ARG70. 2
The unit consists of two parts: · A plastic housing with digital display, which accommodates the electronics, the operating elements and the built-in room temperatures sensor · A mounting base The housing engages in the mounting base and snaps on. The DIP switch is located at the rear of the housing.
3031Z01
3/8 Siemens Building Technologies HVAC Products Room temperature controllers CE1N3031en 24. 09. 2003
Legend
1 2 3 4 5 6 7 8
Display of the room temperature, setpoints or operating mode changeover time symbol when actual room temperature is displayed Normal operation Energy saving mode symbol when displaying the operating mode changeover time or when the operating mode changeover function is activated heating on symbol indicating that batteries need to be replaced (only with battery-powered versions) Buttons for adjusting the setpoint and the operating mode changeover time
Button for operating mode changeover "Normal operation energy saving mode" 9 Button for adjusting the operating mode changeover time 10 Battery compartment (only with battery-powered versions) The required room temperature setpoints for normal operation and energy saving mode and the operating mode changeover time are adjusted with buttons. Operating mode changeover can be triggered by pressing a button. The operating action for the automatic operating mode changeover function is selected with a DIP switch.
DIP switch no. 1 Meaning Operating action of automatic operating mode changeover Position ON Automatic operating mode changeover from normal operation to energy saving mode or OFF Position OFF Automatic operating mode change over from energy saving mode or OFF to normal operation
Notes The room temperature controller should be mounted in a location where the air temperature can be measured as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources. Mounting height is about 1. 5 m above the floor.
The unit can be fitted to a recessed conduit box. · · Only authorised staff may open the controller. The cables used must satisfy the insulation requirements with regard to mains potential
Mounting, installation and commissioning
When mounting the unit, fix the baseplate first. Then, make the electrical connections and fit and secure the cover (also refer to Mounting Instructions). [. . . ] h.
5/8
Control outputs
Functional data
Environmental conditions
Siemens Building Technologies HVAC Products
Room temperature controllers
CE1N3031en 24. 09. 2003
Norms and standards
conformity to EMC directive Low voltage directive C-Tick conformity to EMC emission standard Product standards Automatic electrical controls for household and similar use Electromagnetic compatibility Emissions Immunity Safety class Pollution class Degree of protection of housing Connection terminals for Weight Colour of housing front
N474
89/336/EEC 73/23/EEC and 93/68/EEC AS/NSZ 4251. 1:1994 EN 60 730 1 and EN 60 730 2 - 9 EN 50 081-1 EN 50 082-1 II to EN 60730 normal IP30 to EN 60529 use solid wires or prepared stranded wires 2 x 1. 5 mm2 or 1 x 2. 5 mm2 (min. 0. 5 mm2) 0. 20 kg white, NCS S 0502-G (RAL9003)
General
6/8 Siemens Building Technologies HVAC Products Room temperature controllers CE1N3031en 24. 09. 2003
Connection diagram
L N Q12
Q11
Q11 3V
Q14
N1
Q12
Q14
N1
3031A01
Y1
N
Y1
Nx
N
RDD10
N1 Y1 L, Ln N Room temperature controller Regulating unit Live, AC 230 V Neutral, AC 230 V
RDD10. 1
Lx Q11, Q12 Q11, Q14 Nx Live, AC 24 . . . [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE SIEMENS RDD10
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.