[. . . ] EAP 110
ANNUNCIATOR
INSTALLATION, OPERATING & SERVICE MANUAL
PM058 Rev 2 06/01/18
9087A 198th Street, Langley, BC Canada V1M 3B1 Telephone (604) 888-0110 Telefax (604) 888-3381 E-Mail: info@thomsontechnology. com www. thomsontechnology. com
EAP 110 ANNUNCIATOR
CONTENTS
1.
1. 1. 1. 2.
INTRODUCTION
PRODUCT REVISION HISTORY GENERAL DESCRIPTION
4
4 4
2.
2. 1. 2. 6.
INSTALLATION
GENERAL INFORMATION BATTERY SUPPLY INPUT EXTERNAL CONTACT INPUTS REMOTE COMMUNICATION WIRING ANNUNCIATOR CONTROL WIRING ANNUNCIATOR LOCATION/INSTALLATION
6
6 6 7 7 8 8
3.
3. 1. 3. 2.
DESCRIPTION
LEXAN FACEPLATE PRINTED CIRCUIT BOARD
11
11 12
4.
4. 1. [. . . ] · When communication cables must cross over low or high voltage AC power conductors, the communication cables must cross at right angles and not in parallel with the conductors. For additional information on protection against electrical interference, contact Thomson Technology factory.
2. 5.
ANNUNCIATOR CONTROL WIRING
As a minimum, all control wiring shall conform to the local regulatory authority on electrical installations. Specific wire sizes for typical circuits (of distances up to 1000ft (300m) Ê) are as follows: 2. 5. 1. Remote Communication Wiring
Ê
#14 AWG (2. 5mm2) #16 AWG (1. 5mm2) #22 AWG (0. 34mm2) 8 Conductor Shielded Cable
For distances exceeding 1000 Ft. (300m) consult THOMSON TECHNOLOGY.
2. 6.
ANNUNCIATOR LOCATION/INSTALLATION
The annunciator is to be mounted indoors in a dirt free, dry location away from extreme heat sources on a building wall at a suitable location for operating personnel. The annunciator is to be mounted using four screws. The annunciator must be mounted within 1000 feet wiring distance from the MEC 20/MEC 2 Engine controller using an 8 conductor shielded cable. The standard annunciator is suitable for surface mounting as shown in FIGURE #1. The annunciator is available with an optional adapter plate for flush mounting application as shown in FIGURE #2. Assembly details for the flush mounting adapter are shown in FIGURE #3.
PM058 Rev 2 06/01/18
8
Thomson Technology
EAP 110 ANNUNCIATOR
EAP 110 Rear Cover
6. 0"
1. 0"
6. 0"
4. 0"
4 Rear Cover Mounting Holes 3/16" DIAMETER
4. 0"
1. 0"
EAP 110 SURFACE MOUNTING
Enclosure Depth (from front faceplate) = 3. 0"
G:\ENGINEER\PRODUCTS\EAP110 Surface Mount. VSD
FIGURE #1
Flush Mount Adapter Plate 7. 0" 0. 25"
EAP 110 Rear Cover Cutout
(for 6" x 6" clearance)
6. 125"
6. 50"
7. 0"
6. 125"
4 Faceplate Mounting Holes 3/16" DIAMETER
6. 50"
0. 25"
EAP 110 FLUSH MOUNTING
Enclosure Depth (from front faceplate) = 3. 0"
G:\ENGINEER\PRODUCTS\EAP110 Flush Mount. VSD
FIGURE #2
PM058 Rev 2 06/01/18
9
Thomson Technology
EAP 110 ANNUNCIATOR
Wall Edge (Flush Mounting)
Wall Edge (Surface Mounting)
EAP 110 Rear Cover
6. 0"
3. 0"
EAP Flush Mounting Plate (optional) EAP Front Faceplate
EAP 110 Assembly
(Side View)
G:\ENGINEER\PRODUCTS\EAP110 Assembly. VSD
FIGURE #3
PM058 Rev 2 06/01/18
10
Thomson Technology
EAP 110 ANNUNCIATOR
3.
DESCRIPTION
The EAP 110 Annunciator consists of three parts: a Lexan/faceplate, a printed circuit board (PCB) and a rear cover.
3. 1.
LEXAN FACEPLATE
The Lexan faceplate is shown as in FIGURE #4. The Lexan push-buttons and LED's are connected to the main PCB via plug-in ribbon cable.
EAP 110 Annunciator
Emergency Stop EPS Supplying Load EPS Switch Not in Auto
Spare
(Digital Fault #1)
Overcrank Shutdown
Low Engine Temperature Alarm
W eak Battery Voltage
Spare
(Digital Fault #2)
Overspeed Shutdown
Loss of Speed Signal Shutdown
Low Battery Voltage
Battery Charger AC Fail
(Digital Fault #3)
Low Oil Pressure Alarm
High Engine Temperature Alarm
High Battery Voltage
Low Fuel Level
(Digital Fault #4)
Low Oil Pressure Shutdown
High Engine Temperature Shutdown
Spare
(External Input #2)
Spare
(External Input #1)
Alarm Silence
Lamp Test
Pow er On Com munication Fail
FIGURE #4 Alarm labels on the EAP 110 are removable through slots at the top edge of the Lexan. The alarm labels are grouped in 4 rows of 5 labels each. Alarm Fault circuits labels which are programmable in the MEC 2 or MEC 20 Engine Controller can be relabeled on the EAP 110 Annuciator to correspond accordingly. Alarm Fault circuits lights on the EAP which correspond to nonprogrammable MEC Engine Controller faults (e. g. Emergency Stop) cannot be
PM058 Rev 2 06/01/18
11
Thomson Technology
EAP 110 ANNUNCIATOR
3. 2.
PRINTED CIRCUIT BOARD
The printed circuit board (PCB) is shown in FIGURE #5. The PCB contains the following user interface items:
J1
RJ45 JP3 JP2
Ext 4 Ext 3 Ext 2 Ext 1 GRD BB+
Lexan Connector
EAP 110 PRINTED CIRCUIT BOARD LAYOUT
FIGURE #5 3. 2. 1. TERMINAL BLOCK One terminal block is provided for DC control power, ground and 4 external contact inputs. Refer to the connection diagram in section #7 for further information. COMMUNICATION PORT One RJ45 communication port is provided on the circuit board for interconnection to the MEC 2 or MEC 20 Engine controller. When two EAP 110 annunciators are to be interconnected, a T-splitter RJ45 adapter plug must be installed. FIGURE #7 Indicates the specific fault addressing for Group 2 faults. Fault names for digital faults #5-12 and programmable output #6 will be dependent upon how the connected MEC 20 Engine Controller is programmed. [. . . ] Once the programming mode is terminated, the EAP 110 will resume normal operation. All LED's which are not illuminated indicate that they are programmed as the Horn-Enabled. The factory default setting is Horn-
PM058 Rev 2 06/01/18
19
Thomson Technology
EAP 110 ANNUNCIATOR
6.
SPECIFICATIONS
12V or 24V nominal (+- 20%), negative ground 100 ma (maximum), (+- 20%) RS 422, 4. 8 KBaud, Thomson Technology T-Net Protocol to MEC 2/MEC 20 8 conductor #22 AWG (min) Shielded/Twisted cable (1000 ft Max), Plug-in RJ45 Connector
SUPPLY VOLTAGE SUPPLY CURRENT COMMUNICATION PORT
EXTERNAL CONTACT INPUT TEMPERATURE RANGE ENVIRONMENTAL DIMENSIONS
Close to DC Negative -40 C to +50 Deg C Faceplate NEMA 12, Rear Enclosure NEMA 1 6. 0" W x 6. 0" H x 3. 0" D (Flush mount adapter option (7. 0" w x 7. 0" H)
MOUNTING
Surface Mount (Standard), Flush-mount (Optional) Rear Enclosure conduit box c/w Qty 8 ½" knockouts
Specifications subject to change without notice.
PM058 Rev 2 06/01/18
20
Thomson Technology
EAP 110 ANNUNCIATOR
7.
CONNECTION DIAGRAMS
EAP 110 Annunciator
Ext 1 Ext 2 Ext 3 Ext 4
J1
GRD
J6
Communication Cable**
Expansion Port No Connection Com Port
MEC 2/20 Engine Controller
J7
B+ B-
B+ B-
1000' maximum cable length
External Alarm Sensing contacts (optional use as required)
+ 12-24V Engine Cranking Battery
**8 conductor Shielded Twisted Cable c/w RJ45 connectors. Communication cable wiring must be suitably routed to protect it from sources of electrical interference. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE THOMSON EAP 110
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.