User manual TJERNLUND HSJ,1,2 POWER VENTERS WITH UC1 CONTROL 8506001 REV B 0206
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TJERNLUND HSJ,1,2 POWER VENTERS WITH UC1 CONTROL 8506001 REV B 0206. We hope that this TJERNLUND HSJ,1,2 POWER VENTERS WITH UC1 CONTROL 8506001 REV B 0206 user guide will be useful to you.
Lastmanuals help download the user guide TJERNLUND HSJ,1,2 POWER VENTERS WITH UC1 CONTROL 8506001 REV B 0206.
Manual abstract: user guide TJERNLUND HSJ,1,2 POWER VENTERS WITH UC1 CONTROL 8506001 REV B 0206
Detailed instructions for use are in the User's Guide.
[. . . ] UC1 burner / gas valve interlock rated for 1 H. P. @ 120 VAC.
TJERNLUND PRODUCTS, INC.
1601 Ninth Street · White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 · (651) 426-2993 · FAX (651) 426-9547 Visit our web site · www. tjernlund. com
MODELS AND APPLICATION: HSJ (Gas or Oil) Used as a means of Side Wall Venting gas or oil appliances which require a Post Purge cycle. Used also to co-vent two gas heaters within combined BTU/hr. [. . . ] B 2/06
-SIDE VIEW-
-END VIEW-
-PLAN VIEW-
MOTOR ELECTRICAL DATA Volts 115 Hertz 60 RPM 3000 Watts 95 Amps 1. 26 Therm. Yes MOTOR MECHANICAL DATA DESCRIPTION Shaded Pole Yes Open Yes Int. Fan Cooled Yes BEARINGS Type Sleeve Material Sintered Iron UC1 UNIVERSAL CONTROL Maximum Power Consumption 1/2 Amp @ 120 VAC 50/60 Hz + Venter motor load Pre-Purge: Options (0, 15, 30, 60 seconds) Post-Purge: Factory set at 2 minutes Options (0, 30 seconds; 1, 2, 4, 8, 16 minutes) Dimensions: 5" x 8" (2' electrical whip inc. ) SAFETY / INTERLOCK Fan Proving Switch 5 VDC UC1 board supplied power switched through Fan Prover. UC1 burner / gas valve interlock rated for 1 H. P. @ 120 VAC.
TJERNLUND PRODUCTS, INC.
1601 Ninth Street · White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 · (651) 426-2993 · FAX (651) 426-9547 Visit our web site · www. tjernlund. com
MODELS AND APPLICATION: HS1 (Gas or Oil) Used as a means of Side Wall Venting gas or oil appliances which require a Post Purge cycle. Used also to co-vent multiple heaters within combined BTU/hr. input listed below (requires accessory controls). Includes a Fan Proving Switch and the UC1 Universal Control for 24V, 115V or "dry contact" actuation. LED diagnostics and Pre / Post-purge options are standard with the UC1. HSUL-1 (Discontinued 8/05) HS115-1 & HST-1 (Discontinued 7/02) Replace above models with HS1. reserves the right to make changes to specifications without notification.
HS1 POWER VENTER SPECIFICATIONS
Performance curves
Static pressure (inches H2O) vs CFM (std. NOTE: TO ARRIVE AT TOTAL SYSTEM STATIC PRESSURE REFER TO CURVE AND ADD . 38" TO COMPENSATE FOR VENT HOOD AND WIND RESISTANCE.
1. 00
70°F
. 80
300°F 400°F 500°F
MAXIMUM PIPE LENGTH (FT) AT STACK TEMPERATURE GAS FIRED 300° F 150, 000 200, 000 250, 000 300, 000 150, 000 200, 000 250, 000 300, 000 100' 87' 40' 4' 100' 100' 100' 30' 400° F 60' 57' 12' -100' 100' 92' -OIL FIRED 500° F 35' 27' --100' 100' ---
. 60
MODEL VENT PIPE DIA. BTU / HR INPUT
. 40
. 20
CFM (std air)
20
40
60
80
100
120
140
160
HS1
4"
FAN PROVER SENSOR FAN PROVING PRESSURE SWITCH TOLERANCE: ±1/8" UNLESS OTHERWISE NOTED ADJUSTABLE DAMPER
7 4 I. D. DAMPER ADJUSTMENT ROD
6"
2 1/4
4 I. D. 7 5/8
2 1/16
4 I. D.
7 1/2 1 1/2 5 5/8 DRIP SHIELD 3, 000 R. P. M. SHADED POLE MOTOR 4 3/4 11 3 1/8 1 3 1 1/8 10 3/4
5 1/4
FIGURE 2011038-3
4 5/8
-SIDE VIEW-
-END VIEW-
-PLAN VIEW-
MOTOR ELECTRICAL DATA Volts 115 Hertz 60 RPM 3300 Watts 224 Amps 1. 51 Therm. [. . . ] HSUL-2 (Discontinued 8/05) HS115-2 & HST-2 (Discontinued 7/02) Replace above models with HS2. reserves the right to make changes to specifications without notification.
HS2 POWER VENTER SPECIFICATIONS
Performance curves
Static pressure (inches H2O) vs CFM (std. NOTE: TO ARRIVE AT TOTAL SYSTEM STATIC PRESSURE REFER TO CURVE AND ADD . 38" TO COMPENSATE FOR VENT HOOD AND WIND RESISTANCE.
1. 40 1. 20 1. 00 . 80 . 60 . 40 . 20 300°F 400°F 500°F
70°F
MODEL
VENT PIPE DIA.
BTU / HR INPUT
MAXIMUM PIPE LENGTH (FT) AT STACK TEMPERATURE GAS FIRED 300° F 400° F 100' 100' 100' 72' --100' 100' 100' 100' --OIL FIRED 500° F 100' 100' 67' ---100' 100' 100' ----
CFM (std air)
50
100
150
200
250
300
350
400
6"
350, 000 400, 000 450, 000 500, 000 550, 000 600, 000 350, 000 400, 000 450, 000 500, 000 550, 000 600, 000
100' 100' 100' 100' 94' 15' 100' 100' 100' 100' 100' 67'
HS2
TOLERANCE: ±1/8" UNLESS OTHERWISE NOTED
FAN PROVER SENSOR FAN PROVING PRESSURE SWITCH ADJUSTABLE DAMPER
8 5/8 6 I. D.
DAMPER ADJUSTMENT ROD
8"
6 I. D. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TJERNLUND HSJ,1,2 POWER VENTERS WITH UC1 CONTROL 8506001 REV B 0206
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.