User manual TJERNLUND PAI-G & O RESIDENTIAL LIGHT COMMERCIAL COMBUSTION AIR IN-FORCERS 8500386 REV A 1102

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TJERNLUND PAI-G & O RESIDENTIAL LIGHT COMMERCIAL COMBUSTION AIR IN-FORCERS 8500386 REV A 1102. We hope that this TJERNLUND PAI-G & O RESIDENTIAL LIGHT COMMERCIAL COMBUSTION AIR IN-FORCERS 8500386 REV A 1102 user guide will be useful to you.

Lastmanuals help download the user guide TJERNLUND PAI-G & O RESIDENTIAL LIGHT COMMERCIAL COMBUSTION AIR IN-FORCERS 8500386 REV A 1102.


Mode d'emploi TJERNLUND PAI-G & O RESIDENTIAL LIGHT COMMERCIAL COMBUSTION AIR IN-FORCERS 8500386 REV A 1102
Download
Manual abstract: user guide TJERNLUND PAI-G & O RESIDENTIAL LIGHT COMMERCIAL COMBUSTION AIR IN-FORCERS 8500386 REV A 1102

Detailed instructions for use are in the User's Guide.

[. . . ] The safe and cost-effective way to ensure adequate combustion air for gas and oil-fired heating equipment or to improve air quality problems caused by tight construction. Features of all IN-FORCERS s Installation is fast, simple and economical. s Built-in damper closes during off cycles to prohibit cold air entry and warm air loss. s Uses indoor air to temper outdoor air for increased comfort. [. . . ] s Replaces air vented by exhaust fans, fireplaces, etc. s Reduces moisture, mold and mildew buildup. s Increases security--fresh air is brought in while windows and doors are locked. A B C D 2 5/8" E 8" F 9 3/8" 17 3/4" 15 5/8" 8 7/8" Motor Specifications 115/1/60 1600 RPM 80 WATTS 1. 0 FLA Steps to Selecting the Right Combustion Air IN-FORCER · PAI-1G & PAI-2G for 24 VAC Control Circuits · PAI-1O & PAI-2O for 115 VAC Control Circuits Step 1: Determine the required CFM Step 2: Calculate the equivalent Step 3: Referencing Table C and your calfrom Table A based on equipment type and BTU/hr input of the heater(s). length of 3" PVC inlet pipe and 6" outlet duct (if used) from Table B. culated equivalent length, verify that CFM performance listed in Table C is equal to or greater than that determined in Table A. Select Model PAI-1 or PAI-2 Series based on CFM necessary and control circuit voltage. Required CFM Based on Equipment Type and BTU/HR Input Table A BTU/HR INPUT 40, 000 50, 000 60, 000 70, 000 80, 000 90, 000 100, 000 110, 000 120, 000 130, 000 140, 000 150, 000 160, 000 GAS INDUCED ATMOSPHERIC COMBUSTION 11 21 14 26 17 32 19 37 22 42 25 47 28 53 30 58 33 63 36 68 39 74 41 79 44 ­ OIL FLAME RETENTION 12 15 18 21 24 27 30 33 37 40 43 46 49 BTU/HR INPUT 170, 000 180, 000 190, 000 200, 000 210, 000 220, 000 230, 000 240, 000 250, 000 260, 000 270, 000 280, 000 290, 000 GAS INDUCED ATMOSPHERIC COMBUSTION 47 ­ 50 ­ 52 ­ 55 ­ 58 ­ 61 ­ 63 ­ 66 ­ 69 ­ 72 ­ 74 ­ 77 ­ 80 ­ OIL FLAME RETENTION 52 55 58 61 64 67 70 73 76 79 ­ ­ ­ Calculate Equivalent Length Table B The performance shown is based on equivalent feet. To determine the equivalent feet of an installation, add the length of the 3" PVC inlet pipe plus the equivalent length of any elbows. Do not include intake elbow or gooseneck equivalent loss, they have already been factored into the performance data. Use the same method to determine the equivalent feet if a 6" outlet duct is installed. EQUIVALENT LENGTH OF ELBOWS ELBOW DIAMETER 3" PVC 6" 900 5' 10' 450 2. 5' 5' In-Forcer CFM Performance Data Table C Models PAI-1G & PAI-1O · Models PAI-2G & PAI-2O Conventional straight thru wall intake 6" OUTLET LENGTH 20 FEET 10 FEET 0 FEET 3" PVC INLET LENGTH 2 FEET 10 FEET 15 FEET 20 FEET 59 CFM 53 CFM 50 CFM 47 CFM 80 CFM 68 CFM 65 CFM 60 CFM 56 CFM 50 CFM 46 CFM 44 CFM 75 CFM 65 CFM 62 CFM 57 CFM 52 CFM 47 CFM 41 CFM N/A** 70 CFM 60 CFM 57 CFM 52 CFM Optional gooseneck intake 6" OUTLET LENGTH 20 FEET 10 FEET 0 FEET 3" PVC INLET LENGTH 2 FEET 10 FEET 15 FEET 20 FEET 52 CFM 47 CFM 44 CFM 43 CFM 64 CFM 58 CFM 54 CFM 53 CFM 48 CFM 44 CFM 42 CFM N/A** 62 CFM 54 CFM 52 CFM 49 CFM 46 CFM 42 CFM N/A** N/A** 58 CFM 50 CFM 48 CFM 44 CFM **BELOW FAN PROVER SET POINT *PVC EXTENDED FOR BELOW GRADE APPLICATIONS OR ANTICIPATED SNOW LINE Fresh Air IN-FORCERS Models PAI-1T & PAI-2T The Timer/Clock on the Fresh Air IN-FORCER may be set to operate in one of two ways. Easy-to-follow instructions and examples of these methods can be found in the IN-FORCER'S manual. Life-Style: The IN-FORCER may be cycled according to the occupants' life-style. One scenario would be to set the timer to operate the IN-FORCER for several hours straight in the morning and evening when a family is most active cooking, using bathroom facilities and doing laundry. [. . . ] ELBOW DIAMETER 3" PVC 6" 900 5' 10' 450 2. 5' 5' For larger applications, use Tjernlund Commercial Combustion Air IN-FORCERS. Models available with capacities up to 6000 CFM. Request brochure 8500402. IN-FORCERS are available from: ® TJERNLUND PRODUCTS, INC. 1601 Ninth Street White Bear Lake, MN 55110-6794 Phone: 651. 426. 2993 800. 255. 4208 Fax: 651. 426. 9547 Visit our web site: www. tjernlund. com Copyright © 2002 Tjernlund Products, Inc. [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE TJERNLUND PAI-G & O RESIDENTIAL LIGHT COMMERCIAL COMBUSTION AIR IN-FORCERS 8500386 REV A 1102

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets...
In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.

Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual TJERNLUND PAI-G & O RESIDENTIAL LIGHT COMMERCIAL COMBUSTION AIR IN-FORCERS 8500386 REV A 1102 will begin.

Search for a user manual

 

Copyright © 2015 - LastManuals - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.

flag