If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TJERNLUND PS1503 DUCT AIRSTAT FAN PROVING SWITCH REV A 1099. We hope that this TJERNLUND PS1503 DUCT AIRSTAT FAN PROVING SWITCH REV A 1099 user guide will be useful to you.
Lastmanuals help download the user guide TJERNLUND PS1503 DUCT AIRSTAT FAN PROVING SWITCH REV A 1099.
Manual abstract: user guide TJERNLUND PS1503 DUCT AIRSTAT FAN PROVING SWITCH REV A 1099
Detailed instructions for use are in the User's Guide.
[. . . ] TJERNLUND PRODUCTS, INC.
1601 Ninth Street · White Bear Lake, MN 55110-6794 PHONE (651) 426-2993 · FAX (651) 426-9547 Visit our web site · www. tjernlund. com
OWNERS INSTRUCTIONS DO NOT DESTROY
MODEL PS1503
The Tjernlund Duct Airstat senses positive pressure in a forced air heating and/or cooling system. The single pole, single throw, snap-acting switch is activated by a diaphragm with integral pressure probe inserted directly into the duct or plenum. The Duct Airstat can be used to initiate such auxiliary devices as: Duct Boosters, Electronic Air Cleaners, Electrical Duct Heaters, and Humidifiers. [. . . ] Sealing gasket must be mounted on pressure probe to ensure minimal air leakage.
1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage. All wiring must comply with applicable codes and ordinances. Always conduct a thorough checkout when installation is complete.
WIRING:
All wiring must agree with applicable electrical codes and ordinances. Typical diagrams are shown below.
Duct Airstat Duct Booster Electronic Air Cleaner Electronic Duct Heater
Humidifier
115-120V
TYPICAL MOUNTING LOCATIONS & APPLICATIONS
SIDE VIEW
SWITCH MUST BE MOUNTED WITH DIAPHRAGM IN VERTICAL POSITION
TOP VIEW
Branch Run
Plenum Duct Booster
Trunk Line
A
B
Switch activates Duct Booster by sensing positive pressure on either plenum, trunk, or branch lines as shown in Figures A and B above.
ELECTRONIC AIR CLEANERS
HUMIDIFIERS
FAN OPERATION
Switch proves operation of blower by sampling positive pressure.
Switch actuates air cleaner by sensing positive plenum pressure.
Switch activates humidifier by sensing positive plenum pressure.
CONNECTING TO SCREW-IN TERMINALS:
To connect to screw-in terminals, use the following procedures: 1. 14 or 16 stranded wire may be connected to these terminals. Do not connect aluminum wire to the screw-in terminals on this device. Strip insulation from wires approximately 1/2". Bend each bare lead around its respective terminal in a clockwise direction and tighten terminal screw. Replace the electrical box cover when connections are complete.
GENERAL SPECIFICATIONS:
ELECTRICAL RATING: 278 VA Pilot Duty at 24 Volts AC 300 VA Pilot Duty at 115 to 277 Volts AC 15 AMPS Non-Inductive to 277 Volts AC ELECTRICAL SWITCH: SPST, N/O, Snap Action Contacts, Non Adjustable OPERATING PRESSURE / POSITION: On pressure rise at +. 05 + . 02" W. C. (Diaphragm Vertical) MAXIMUM PRESSURE: 1/2 PSI OPERATING TEMPERATURE RANGE: -40 to 1900 F. OPERATING POSITION: Diaphragm must be vertical PRESSURE PROBE: Self-sealing, integral pressure probe DIMENSIONS: 5" Diam. , 5 1/2" Across Bracket, 3" High
TROUBLE-SHOOTING:
Installations in larger ducts or "dead spots" in duct work may not create enough positive pressure "impact" to activate the Duct Airstat. Try locating pressure probe at several points. Contact Tjernlund Products customer service @ 1-800-255-4208 or email us at fanmail@tjfans. com for further assistance.
OTHER TJERNLUND PRODUCTS
HIGH PRESSURE DUCT FANS
DUCT BOOSTER® DUCT & EXHAUST FANS
TJERNLUND LIMITED ONE YEAR WARRANTY Tjernlund Products, Inc. warrants to the original purchaser of this product that the product will be free from defects due to faulty material or workmanship for a period of (1) year from the date of original purchase or delivery to the original purchaser, whichever is earlier. Remedies under this warranty are limited to repairing or replacing, at our option, any product which shall, within the above stated warranty period, be returned to Tjernlund Products, Inc. [. . . ] Send all inquiries regarding warranty work to Tjernlund Products, Inc. 1601 9th Street, White Bear Lake, MN 55110-6794. Phone (651) 426-2993 · Fax (651) 426-9547. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TJERNLUND PS1503 DUCT AIRSTAT FAN PROVING SWITCH REV A 1099
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual TJERNLUND PS1503 DUCT AIRSTAT FAN PROVING SWITCH REV A 1099 will begin.