Manual abstract: user guide TOSHIBA BMS-IFDD01EINSTALLATION MANUAL
Detailed instructions for use are in the User's Guide.
[. . . ] · After the installation work, perform a trial operation to check for any problem. Follow the Owner's Manual to explain how to use and maintain the unit to the customer. Ask the customer to keep this Installation Manual together with the Owner's Manual.
WARNING
· Ask an authorized dealer or qualified installation professional to install or reinstall the relay interface. [. . . ] If connected with incorrect polarity, the unit will not work.
REQUIREMENT Install a breaker at the primary side of the power supply.
Power cables/Earth wires/Signal wires
Connect power cables, earth wires, and signal wires to the specified terminals on the terminal block.
Secure each cable with a cable clamp.
SW3
ON 1234
SW4
SW7
Connect the earth wire to the earth terminal on the chassis. Power cable
N L
DI4
DI3
DI2
DI1
SW1
SW2
A B FG
DI8
DI7
DI6
DI5
Digital input contacts
Intelligent server
DO1 DO2 DO3 DO4 GND +12V
RS-485
Digital output load
Length of stripped power cable
35 10
Length of stripped communication wire
35 6
Length of stripped digital Input/Output connector wire
35 6
55
10
Insert the wire by pushing the lever with a screwdriver. Check that the wire is inserted securely.
When inserting two RS-485 communication cables into a single terminal for connection to another interface, crimp them using the attached pin terminal.
5
2
Connection of Power cables/Earth wires/ Signal wires (continued)
CAUTION
Wiring Connection
If an inductive load (relay coil) or a bulb is connected, a surge voltage or rush current will be generated. Take adequate measures against surge voltage or rush current. The following describes wiring connections of the Digital Input/Output Relay Interface when it is used in the air conditioner control system.
· Terminator resistor setting
Set the RS-485 terminator resistor by the TCS-NET Relay Interface. Do not set it by the Digital Input/Output Relay Interface.
· Shield earthing
The shield earth of the RS-485 signal wires should be single-point earth. Earth the wires on the Intelligent Server. Other shield lines should be closed, and the terminal end should be open and insulated.
· Connection of external digital inputs
Input circuit examples are shown below (electrically isolated using a photo-coupler). (1) Example of contact input connection
12V
(2) Example of current sink connection
12V
Input terminal DI-1 to DI-8 Contact
Input terminal DI-1 to DI-8 Current sink
· Connection of external digital outputs
Output circuit examples are shown below (open collector output electrically isolated using a photocoupler). (1) Example of load connection
12V Output terminal DO1 to DO4 Load External power supply
(2) Example of load connection
12V +12V
GND
Output terminal DO1 to DO4
6
2
Connection of Power cables/Earth wires/ Signal wires (continued)
Crimp 3 wires with a closed end wire joint. Yellow Brown
Connection diagram
A U2 U1 FG NL B
B
Red A Orange
INTELLIGENT SERVER (BMS-LSV2E)
Red/Orange
TOUCH SCREEN CONTROLLER (BMS-TP0640/5120)
Brown/Yellow
Power supply
A B
RS-485
TCC-LINK
Connect the shield wire of the two wires
TCS-NET RELAY INTERFACE
SW1
4
ADDRESS
DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8
Input contact 1 Input contact 2 Input contact 3 Input contact 4 Input contact 5 Input contact 6 Input contact 7 Input contact 8 The RS-485 signal wire has polarity A and B. Load 1 Load 2 Load 3 Load 4
Power supply
The shield earth of the RS-485 signal wires should be single-point earth. Earth the wires on the Intelligent Server.
NL
Set the Digital Input/Output Relay Interface address with SW1. Assign 1 to 4 to each address to avoid duplication. [. . . ] Displays DI-8 input status.
· Checking external output connection In the test mode, you can set output terminals DO1 to DO4 to ON or OFF with the test switch. Their output status is indicated by each LED. Checking procedure: Set the operation mode switch SW2 to "3" in the same way as the external input check, and then push the reset switch SW7 to enter the test mode. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA BMS-IFDD01E
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.