User manual TOSHIBA BMS-STCC01E INSTALLATION MANUAL
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TOSHIBA BMS-STCC01E. We hope that this TOSHIBA BMS-STCC01E user guide will be useful to you.
Lastmanuals help download the user guide TOSHIBA BMS-STCC01E.
Manual abstract: user guide TOSHIBA BMS-STCC01EINSTALLATION MANUAL
Detailed instructions for use are in the User's Guide.
[. . . ] 1 Elements of the Intelligent Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1 CF (Compact Flash) card Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2 Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] Check the following package contents.
No. 1 2 3 4 Item Intelligent Server Software Cable Closed end wire joint Installation Manual Quantity Remarks 1 Compact Flash card 1 RS-485 cable for Intelligent Server 2 1
Use the following wiring materials to connect signal lines. 1 Signal line For RS-485 Description Type 2-core shield wire Wire size 1. 25 mm2, 500m max. (total length) Length
1
Elements of the Intelligent Server
Front view INTELLIGENT SERVER
RUN LED (green) LON T/R LED (green) END LED (green) General-purpose LED1 (green) General-purpose switch 2 General-purpose switch 1 Maintenance switch Shutdown request switch Reset switch LON service switch General-purpose LED2 (green) Error indication LED (red) SERVICE LED (green) INITIALIZE LED (red)
Perspective view INTELLIGENT SERVER
AC inlet (AC IN) Power switch (POWER) Serial port 2 (PORT 2) Serial port 1 (PORT 1) Ethernet port 2 (Ethernet 2) Ethernet port 1 (Ethernet 1)
Specification of Installation Environment (1) Ambient Conditions
The specification of ambient conditions is shown below. Ambient Specification
Item Temperature Temperature Change Humidity Vibration Shock Operation 0 to 40 °C 15 °C/H 10 to 90 %RH (without condensation) 2. 45 m/s2 or the less 24. 5 m/s2 or the less Storage -20 to +60 °C 15 °C/H 10 to 90 %RH (without condensation) 4. 91 m/s2 or the less 49. 0 m/s2 or the less
(2) Power Supply Conditions
The specification of power supply conditions is shown below. Power Supply Specification
Item Rated Voltage Power Supply Tolerable Range Frequency Tolerable Power Interruption Specification 100/240 V, AC Single phase with grounding 85 - 132 V, AC / 180 - 264 V, AC 50/60 Hz ± 3 Hz, or the less 20 ms, or the less Exclusive grounding (Grounding resistance: 100 ohms, or the less)
Grounding
2
1
CF (Compact Flash) card Installation
REQUIREMENT · Do not insert or remove the CF (Compact Flash) card during power on of the Intelligent Server. · If the CF (Compact Flash) card is not inserted properly, the Intelligent Server will not work.
Insert the attached CF (Compact Flash) card fully into the CF (Compact Flash) card slot on the side of the Intelligent Server.
CF (Compact Flash) card
CF (Compact Flash) card slot
2
1 OFF
Setting
RS-485 operation mode setting
The RS-485 mode set switch is provided on the bottom board of the Intelligent Server. Set the switch as follows:
2 ON 3 ON 4 OFF
ON
AC inlet side
1 2 3 4
LED indicator side RS-485 mode set switch
1 2 3 4
1 2
NOTE If the RS-485 mode set switch is set incorrectly, the Intelligent Server will not work.
3 4
ON OFF ON OFF ON OFF
A terminator resistor is connected between TX(+) and TX(-). No terminator resistor is connected between TX(+) and TX(-). A terminator resistor is connected between RX(+) and RX(-). No terminator resistor is connected between RX(+) and RX(-). Half-duplex mode (Note 1) Full-duplex mode (Note 2)
Not used
(Note 1) Transmit data sent from the Intelligent Server is not received by the same server during transmission. (Note 2) Transmit data sent from the Intelligent Server is also received by the same server during transmission.
3
3
Installation
Intelligent Server Installation Method and Orientation
There are four ways to install the Intelligent Server as shown below: (1) rack mount (2) surface mount (3) wall mount A, and (4) wall mount B. The rack mount installation requires a support bracket for a 19-inch rack. Please contact us if you need the support bracket. Use the four bottom screw holes for the wall mount installation. (1)Rack mount A support bracket is required to be fixed to the bottom (rear side) of the unit. (2)Surface mount Standard installation
(3)Wall mount -A Wall mount with the front side upward
(4)Wall mount -B Wall mount with the left side upward
(Unit: mm)
30. 8 308. 4 30. 8
AC inlet side
LED side
REQUIREMENT Do not install the unit in any of the following places. · Humid or wet place · Dusty place · Place exposed to direct sunlight · Place where there is a TV set or radio within one meter · Place exposed to rain (outdoors, under eaves, etc. ) 4
30
133
35
Screw hole for wall mount (M4 × 4 pcs. )
3 Installation
Installation Space
(continued)
Installation Space and Maintenance Space
The installation space and the maintenance space must be determined before installation. These spaces depend on installation method.
The values in the following table are required for installation space in each direction. [. . . ] The brown and yellow wires can be connected directly to the terminal board RS-485 B of the Relay Interface.
INTELLIGENT SERVER
Ethernet1 PORT1
Closed end wire joint
NOTE The RS-485 signal wire has polarity. If connected with incorrect polarity, the unit will not work. Do not connect or disconnect the wire during control operation. Doing so may cause a malfunction.
Attached wire Block diagram of PORT 1
RTS TXD 1 RXD 3 ON OFF100 ohm RX(+) RX(-) 2 ON 100 ohm 10k ohm 5 TX(+) TX(-) Red 2 1 Brown Orange
3 4
Red/Orange Brown/Yellow
TxRx(+) TxRx(-) Connect the shield wires of the 2 wires
RS-485
RS-485
TCS-NET Relay Interface BMS-IFLSV1E
AB
Yellow
Shield wire open (insulated)
TCS-NET Relay Interface BMS-IFLSV1E
RS-485
AB
6
Appearance and Size
370
WARNING
Do not decompose.
Unit in mm
NOTE Trial operation should be checked by professional service personnel.
Trademarks: · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · Compact Flash and CF are trademarks of SanDisk Corporation. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA BMS-STCC01E
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.