[. . . ] Document: VF010H08A
INSTRUCTION MANUAL
INSTALLATION - OPERATION - MAINTENANCE
HCV-6KAU Vacuum Contactor, 7. 2kV 720A 7. 2kA HCV-6KALU Vacuum Contactor, 7. 2kV 720A 7. 2kA
Issued: 12/05 Manufactured in the USA
TOSHIBA INSTRUCTION MANUAL
For the Installation, Operation and Maintenance of
HCV-6KAU Vacuum Contactor, 7. 2kV 720A 7. 2kA HCV-6KALU Vacuum Contactor, 7. 2kV 720A 7. 2kA
WARNING Never attempt to install, operate, maintain or dispose of this equipment until you have first read and understood all of the relevant product warnings and user directions that are contained in this Instruction Manual.
To contact Toshiba, address all correspondence to: Field Service Department Toshiba International Corporation 13131 West Little York Road Houston, Texas 77041 USA or call: (713) 466-0277 (800) 231-1412 (800) 527-1204 (Canada) Fax: (713) 466-8773 Please complete the following information for your records and retain with this manual: Model: ___________________________________ Serial Number: _____________________________ Date of Installation: _________________________ Inspected by: ______________________________ Reference Number: _________________________ © TOSHIBA INTERNATIONAL CORPORATION, 2004
SAFETY
Page 1
IMPORTANT MESSAGES Read this manual and follow its instructions. Signal words such as DANGER, WARNING and CAUTION will be followed by important safety information that must be carefully reviewed. DANGER Indicates a situation which will result in death, serious injury, and severe property damage if you do not follow instructions. Means that you might be seriously injured or killed if you do not follow instructions. [. . . ] Closing Supply AC/DC
R
S
T
Vacuum Bottles U V W 16 T4 T3 T2 Diode T1 26 25 24 23 Auxiliary Switch 22 21 15 14 13 12 11
Tripping Supply DC
52 CC
52 CC
52 TC
5
Drive Unit
6 2
A2
1
A1
Closing Supply AC/DC
Figure 7 Internal connection of the latched type
LEGEND Re mo t e Op e r a t i o n Swi t ch OF F OF F ON ON Local CR 52 CC . . . . Control Relay
CR VCTT A1 16 R e mo t e St ar t I nt er l ock Dr i ve Un i t 15 14 13 12 11
AC/DC 100/110V 200/220V
CR
Auxi l i ar y Swi t c h
T1 26 25 24 23 22 21
St op I nt erl ock Dr S ( Do o r Sw i t c h ) 2 E ( Over l oa d) A2 CR
52 CC
52 CC
GL T2
RL
Figure 8 Standard operation circuit of the normally energized type
PRE-ENERGIZATION CHECK
Remo t e Op er at i o n Swi t c h
Page 15
LEGEND 52 CC . . . . . Closing Supply AC/DC
OFF CR 2E ON ON CR VCTT A1 L oca l 100/110V 200/220V 11 Remo t e St ar t I nt e r l o ck 15 14 13 12 T4
AC/DC
Dr i ve Un i t
T1
21
25
24
23
22
16 D 26 GL T2 CR A2 T3 RL 52 CC 52 CC 52 TC
Figure 9 Standard operation circuit of the latched type (shunt trip)
Remot e Oper at i on Swi t c h
LEGEND 52 CC . . . . . Vacuum Contactor
OFF CR ON ON CR VCTT A1 Local 11 100/110V 200/220V Remot e 15 14 13 12 CTD P N Dr i ve Uni t T1 U V T4 2E
AC/DC
St ar t I nt er l ock
21
25
24
23
22
16 D 26 GL T2 CR A2 T3 RL 52 CC 52 CC 52 TC
Figure 10 Standard operation circuit of the latched type (capacitor trip)
Page 16
MAINTENANCE PROGRAM
MAINTENANCE
MAINTENANCE RECORD
In order to ensure continued reliable and safe operation of the equipment, a program of periodic maintenance must be established. Operating and environmental conditions will usually dictate the frequency of inspection required. NFPA Publication 70B "Electrical Equipment Maintenance" may be used as a guide for setting up the maintenance program.
DANGER Contact with energized components can cause severe injury, death and property damage. Turn off and lock out primary and control circuit power before servicing. Improper maintenance can cause severe injury, death and property damage. Only qualified and authorized persons are to install, operate or service this equipment. Do not allow grease or any other substances to contaminate insulating materials. Contaminated insulators can allow a short circuit or ground fault to occur.
Keep a permanent record of all maintenance work. At a minimum, this record should include information on: 1. Items inspected Reports of any testing Equipment condition Corrective actions or adjustments Date of work Comments
The degree of detail of the record will depend somewhat on the operating conditions.
SERVICING EQUIPMENT
WARNING
For your safety, turn off and lock out main and control circuit power before servicing the contactor. Certain minimum safety procedures must be followed: 1. Only qualified personnel should attempt this service. Never perform service on or next to exposed components energized with line voltage.
WARNING Failure to adhere to these safety procedures can result in severe injury, death and property damage.
WARNING
NOTE:
Refer to the SAFETY section of this manual for important information.
MAINTENANCE
RECOMMENDED INSPECTION AND MAINTENANCE TYPES NOTE: Table 1 - Tightening Torque Screw Nominal Diameter
Page 17
Tightening Torque
Refer to the SAFETY section of this manual for important information.
1. Acceptance Inspection This inspection confirms that the contactor is complete, correct as specified and undamaged from shipment. The procedure for this inspection is outlined in the RECEIVING, INSPECTION AND HANDLING section of this manual. Patrol Inspection Inspection is made of the condition of the contactor while it is energized. Check that no unusual sounds or smells exist externally. Check for any abnormal discoloration due to overheating. Inspect for signs of damage to the insulation frame, OPEN/CLOSE indicator and other components. [. . . ] The mechanical service life of the vacuum interrupters is 200, 000 operations. For the components in Table 4, replacement or detailed inspection and cleaning are recommended after the indicated number of operations.
Stationary Core
Closing/Trip Coil Flexible Conductor
Switching Life (ten thousand)
10
8 6 4
A
Figure 13 - Wipe Measurement
2
1 10
20
40
60
100
200
400 600 1000
Switching Current (A)
Figure 14 - Capacitor Switching Life
Page 24
STORAGE
STORAGE AND DISPOSAL
If the contactor is to be stored for any length of time prior to installation, the following precautions should be taken. The original packing should be restored, if possible. Do not subject the equipment to moisture or sunrays. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA HCV-6KAU Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service. Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual TOSHIBA HCV-6KAU will begin.