Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TOSHIBA HWS-1103H-E. We hope that this TOSHIBA HWS-1103H-E user guide will be useful to you.
Lastmanuals help download the user guide TOSHIBA HWS-1103H-E.
You may also download the following manuals related to this product:
TOSHIBA HWS-1103H-E DATA BOOK (28610 ko)
Manual abstract: user guide TOSHIBA HWS-1103H-ESERVICE MANUAL
Detailed instructions for use are in the User's Guide.
[. . . ] A10-006
AIR TO WATER HEAT PUMP
SERVICE MANUAL
Model name:
Hydro Unit
HWS-803XWHM3-E(TR) HWS-803XWHT6-E(TR) HWS-803XWHD6-E HWS-803XWHT9-E HWS-1403XWHM3-E(TR) HWS-1403XWHT6-E(TR) HWS-1403XWHD6-E HWS-1403XWHT9-E(TR)
Outdoor Unit
HWS-803H-E(TR) HWS-1103H-E(TR) HWS-1403H-E(TR) HWS-1103H8-E HWS-1103H8R-E HWS-1403H8-E HWS-1403H8R-E HWS-1603H8-E HWS-1603H8R-E
Hot Water Cylinder
HWS-1501CSHM3-E(-UK) HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK)
Contents
1 SAFETY PRECAUTIONS . 6
2-1. Safety During Installation and Service . 7 2-2-2. Processing of piping materials . 22 5-2. Outdoor Unit (Single phase Type) . [. . . ] The outlet temperature error When the discharge temperature sensor (TD) exceeds 111°C.
O
× ×
1
111
L29
O
1. Replace the outdoor control board.
1
111
P03
O
× × ×
1. Check the refrigeration cycle (gas leak). Check the resistance value of the discharge temperature sensor (TD).
4
112
P04
The high pressure switch error The power supply voltage error When the power supply voltage is extremely high or low. Overheating of heat-sink error When the heat-sink exceeds 105°C.
O
10 1. (AC220-230 V±10 %: single phase type). (AC380-400 V±10 %: 3 phase type). Check the thread fastening and heat-sink grease between the outdoor control board and the heatsink. Check the resistance value of the heat-sink temperature sensor (TH). Check the refrigeration cycle (gas leak). Check that the service valve is fully open. Check the resistance value of the discharge temperature sensor (TD) and the suction temperature sensor (TS). Check the operation of the 4-way valve unit or the coil characteristics. Check the resistance value of the heat exchange temperature sensor (TE) and the suction temperature sensor (TS).
113
P05
O
4
114
P07
O
×
4
114
P15
Detection of gas leak When the discharge temperature sensor (TD) exceeds 106°C for consecutive 10 min. When the suction temperature sensor (TS) exceeds 60°C for cooling or 40°C for heating for 10 consecutive min.
O
×
4
115
P19
The 4-way valve inversion error When the heat exchange temperature sensor (TE) exceeds 30°C or the suction temperature sensor (TS) exceeds 50°C during the heat pump operation.
O
×
4
116
88
Diagnostic functional operation Check code Operational cause Backup Automat present ic reset Determination and action
Number of abnormalities Detailed for item confirmation
P20
High pressure protection operation When an abnormal stop occurs due to the high pressure release control. When the heat exchange temperature sensor (TL) detects 63°C during the cooling operation. When the water outlet sensor (TWO) detects 60°C during the heating or hot water supply operation. Outdoor fan system error When a DC fan rotor position detection NG, element short circuit, loss of synchronization, or abnormal motor current occurs.
O
×
1. Check that the service valve is fully open. Check the outdoor fan system (including clogging). Check the resistance value of the heat exchange temperature sensor (TL) and the water outlet temperature sensor (TWO). Check the connection of the fan motor cable connector. [. . . ] Operation frequency (Outdoor unit operation check) 4. Air heat exchanger inspection (Dirt and clogging) 6. Cycle parts (Compressor, 4-way valve, Pulse motor valve) 8. Inverter control board, Terminal block
Frequency
Annually Annually
Periodic inspection details
Insulation measurement with a mega tester Electronic voltage measurement: 220-230V ±10% (Single phase type) 380-400V ±10% (3 phase type) Frequency check by rated operation (See 10-13) Visual inspection and check connection with a leak tester: No leakage must be found Visual inspection, Clear clogging Check for scratches or damages to the fan or abnormal motor sound Operation check by trial run Check for loose connector and connecting terminal
Annually Annually Annually Annually Annually Annually Annually
Hot water cylinder (HWS-150CSHM3-E(-UK), 210CSHM3-E(-UK), 300CSHM3-E(-UK))
1. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA HWS-1103H-E
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.