Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TOSHIBA MCY-MAP0601HT. We hope that this TOSHIBA MCY-MAP0601HT user guide will be useful to you.
Lastmanuals help download the user guide TOSHIBA MCY-MAP0601HT.
You may also download the following manuals related to this product:
TOSHIBA MCY-MAP0601HT DATA BOOK (13101 ko)
TOSHIBA MCY-MAP0601HT DESIGN MANUAL (9277 ko)
TOSHIBA MCY-MAP0601HT SERVICE MANUAL (6589 ko)
TOSHIBA MCY-MAP0601HT INSTALLATION MANUAL (13105 ko)
Manual abstract: user guide TOSHIBA MCY-MAP0601HTQUICK REFERENCE
Detailed instructions for use are in the User's Guide.
[. . . ] FILE NO : A06-007
Quick reference
R410A
01
Refrigerant Piping
Allowable length/height difference of refrigerant piping
Outdoor unit
Main pipe L1
Branching pipe L2
1st branching section Height difference between indoor and outdoor units H1
Branch header
a
b
c
d
Branching pipe L3
Indoor unit
Equivalent length corresponded to farthest piping L
Equivalent length corresponded to farthest piping after 1st branching Li
Height difference between indoor units H2
L4 e Y-shape branch joint f g
A *1
Allowable value Total extension of pipe (Liquid pipe, real length) Furthest piping length L (*1) Piping Length Real length Equivalent length 180 m 100 m 125 m 65 m 35 m 15 m 30 m 20 m 15 m
Piping section L1 + L2 + L3 + L4 + a + b + c + d + e + f + g L1 + L3 + L4 + g
Max. equivalent length of main pipe Equivalent length of furthest piping from 1st branching Li (*1) Max. real length of indoor unit connecting pipe Height between indoor and outdoor units H1 Upper outdoor unit Lower outdoor unit
L1 L3 + L4 + g a, b, c, d, e, f. g ------ ------ ------
Height Difference
Height between indoor units H2
*1 : Furthest indoor unit from 1 branch to be named "A".
st
02
Allowable length/height difference of refrigerant piping for quiet places (with PMV Kit)
Outdoor unit
Main pipe L1
Branching pipe L2
1st branching section
Branch header a b c d
PMV Kit
Height difference between indoor and outdoor units H1
h Branching pipe L3
i
j
k
Indoor unit
Height difference between indoor unit and PMV Kit H2 * * Between highest unit and lower units. [. . . ] (15 to 18V usually) Countermeasures
Remote controller status No response
No display on remote controller (No line is output. )
None
The power is not turned on. (Unit which is not displayed on remote controller) Remote controller is not connected with cable. (Unit which is not displayed on remote controller) Miscabling of remote controller (Unit which is not displayed on remote controller) Remote controller communication circuit error (Unit which is not displayed on remote controller) If 230V is incorrectly applied to the remote controller terminal, the remote controller communication circuit fails.
4
In check for No. of connected Indoor units after address setup, diminished No. (There are outdoor/indoor units which do not operate in a test operation. )
Status Cause Miswiring of communication line unconnected cable. (Address setup operation has finished without recognition of miswired follower unit. ) Miswiring of communication line between indoor units or unconnected cable. (Address setup operation has finished without recognition of miswired indoor unit. ) Remote controller is not connected with wire. Miscabling of remote controller Remote controller communication circuit error If 230V is incorrectly applied to the remote controller terminal, the remote controller communication circuit fails. Countermeasures After modification of wiring, set up address again and check No. After modification of wiring, set up address again and check No. of the connected indoor units.
Number of connected is short. Number of connected indoor units is short. Number of outdoor units connected to group is short in group operation from remote controller.
Using the main remote controller connected to a group, start a test operation, specify the unit which does not operate (Unit unconnected to group), and then check wiring. Using the main remote controller connected to a group, start a test operation, specify the unit which does not operate (Unit unconnected to group). Remove Fasten receptacle connected to remote controller terminals (A/B), and check the voltage. If voltage is not applied, replace P board. (15 to18V in normal time)
17
Monitor Function of Remote Controller Switch
When using a remote controller with the model name RBC-ATM21E, the following monitor functions can be used. Calling of display screen [Contents]
The temperature or the operation status of the remote controller, indoor unit, or each sensor of the outdoor unit can be known by calling up the service monitor mode from the remote controller.
[Procedure]
1 2 3 4
Push CL + TEST buttons simultaneously for 4 seconds or more to call up the service monitor mode. The service monitor goes on, and temperature of the item code 00 is firstly displayed. Push the temperature setup / buttons to select the item number (Item code) to be monitored. For displayed codes, refer to the table below. Push UNIT button to change the item to one to be monitored. [. . . ] Check connector CN30 Check connector CN31
[Close fully]
Short-circuit CN31 on the interface P board of the . C. outdoor unit.
[Clear]
After 2 minutes, the opening returns to the normal operation. Be sure to remove the short circuit after confirmation.
10
Solenoid Valve Forced Open/Close Function in Outdoor Unit
This function is provided to forcibly open/close each solenoid valve mounted in the outdoor unit by use of the switches provided on the outdoor unit interface P board. This function confirms the operation of each solenoid . C. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA MCY-MAP0601HT
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual TOSHIBA MCY-MAP0601HT will begin.