SERVICE MANUAL
Mini-SUPER MODULAR MULTI SYSTEM AIR CONDITIONER
Outdoor Unit
[Inverter Unit]
MCY-MAP0401HT, HTZ, HTZG MCY-MAP0501HT, HTZ, HTZG MCY-MAP0601HT, HTZ, HTZG MCY-MAP0401HT2D, HT2DZ, HT2DZG MCY-MAP0501HT2D, HT2DZ, HT2DZG MCY-MAP0601HT2D, HT2DZ, HT2DZG
PMV Kit
RBM-PMV0361E RBM-PMV0901E
In addition to description for the normal-type model, descriptions about the models with anti-corrosion (based on JRA Standard light protection and heavy protection) models are added in this Manual.
PRINTED IN JAPAN, Sep. , 2006 ToMo
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. [. . . ] Batch start/stop (ON/OFF) function
This function is provided to start/stop collectively all the indoor units connected to the same system by using switches on the interface P board of the outdoor unit. . C.
Operation procedure
Power ON
Be sure to turn on power at the indoor side before power-ON of outdoor unit. If an error is already displayed under condition of SW01 [1], SW02 [1], SW03 [1], resolve the problem using the troubleshooting guide and then execute the test operation. If the operation is set "heat", indoor unit which is set to "cool priority" will not operate or will be displayed. If the operation is set to "cool", indoor unit which is set to "heat priority" will not operate or will be displayed.
Set up the operation mode of the remote controller. (If it is not set up, the operation continues in the current mode. ) (FAN/COOL/HEAT)
Set on the interface P. C. board of the outdoor unit SW01 to [2], Sw02 to [7], and SW03 to [1] respectively. ([CH ] is displayed on 7-segment display [A]. )
Push SW04 on the interface P. C. board of the outdoor unit for 2 seconds or more.
Start
The indoor unit to be started operates.
Push the push-switch SW05 on the interface P. C. board of the outdoor unit for 2 seconds or more.
Stop
After test operation, return the rotary switches SW01, SW02, and SW03 on the interface P. C. board of the outdoor unit to [1], [1], [1] respectively.
End
99
1st revised : Jun. Individual start/stop (ON/OFF) individual test operation function
This function is provided to start/stop (ON/OFF) individually each indoor unit connected to the same system by using switches on the interface P board of the outdoor unit. Set SW01 [16] and set SW02, SW03 to indoor address No. (1 to 64) to be started (Refer to the following table) - only the setup indoor unit starts operation. (In the rotary switches of the indoor unit which operates in a group by the remote controller, the follower unit cannot be individually started or stopped. In this case, [ ] is displayed on 7-segment display [B] on the interface P board of the outdoor unit. ) . C.
Operation procedure
Power ON
Be sure to turn on power at the indoor side before power-ON of outdoor unit. If an error is already displayed under condition of SW01 [1], SW02 [1], SW03 [1], return the status to normal one according to troubleshooting and then execute a test operation. The unit which is not given with priority by heating priority control, cooling priority control, and selection of cooling or heating mode is not operated. In this case, or is displayed on the remote controller.
Set up the operation mode of the remote controller. (If it is not set up, the operation starts with the current mode. )
Match the rotary switch on the interface P. C. board of the outdoor unit * with in the following table. (7-segment display) [A] [ ] [ [B] ]
Address display of corresponding indoor unit
[ 00] is displayed for 5 seconds after operation-ON.
Push the push-switch SW04 on the interface P. C. [. . . ] 31 32 35 37 40 42 46 47 48 49 50 51 56 60 Part No. 4311M538 43149359 43194077 43119390 43032441 43100347 43100352 43100370 43100371 43100372 43097212 43047669 43063317 43019904 Description Mark, TOSHIBA Socket, DIA 19. 115. 9 (MAP0601) Socket, 1/8 IN Hanger Nipple, Drain Panel, Front, Piping Panel, Air Outlet Panel, Front Panel, Side Panel, Roof Nut Nut, Flange Holder, Thermostat Holder, Sensor
Fan, Propeller, PE492 Guard, Fin Bell Mouth, Plastic Guard, Fan Compressor, DA420A3F-20M2 Heater, Crank Case, AC240V, 24W Heater, Case, 29W, 240V Holder, Sensor Motor, Fan, ICF-140-63-2R Accumulator, 7L Panel, Back, Piping Condenser Ass'y, Down Condenser Ass'y, Up Owner's Manual
189
15-1-2. Refrigeration Circuit
16, 20 22, 44, 59 58 64 54 13 19, 21 34 29
34 14 15, 17 22, 43, 45
39 23 16, 18 36 16, 20 55 57 53 22, 43, 44 34 53 53 6, 56 5 24 28
38 33
7
Location No. 5 6 7 12 13 14 15 15 16 16 17 18 19 20 21 22 23 24 26 Part No. [. . . ]