If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TOSHIBA MMD-AP0181SPH. We hope that this TOSHIBA MMD-AP0181SPH user guide will be useful to you.
Lastmanuals help download the user guide TOSHIBA MMD-AP0181SPH.
You may also download the following manuals related to this product:
TOSHIBA MMD-AP0181SPH SERVICE MANUAL (4494 ko)
Manual abstract: user guide TOSHIBA MMD-AP0181SPHDATA BOOK
Detailed instructions for use are in the User's Guide.
[. . . ] 2005
Engineering Data Book
Slim Duct Type
Contents
Specifications Electrical current characteristics Dimensions Sensible capacity table Wiring diagrams Fan characteristics Sound characteristics (NC Curve) Fresh air intake (Design guide)
Specifications
50Hz
Model name Cooling/Heating capacity Electrical characteristics Power supply Running current Power consumption Starting current Appearance Dimension Height Width Depth Total weight Heat exchanger Soundproof / Heat-insulating material Fan Standard air flow High (Med. /Low) Motor External static pressure (m /h) (m /h) (W) (Pa) 6 (Factory setting) -16-31-46 4steps Air filter pressure los Controller Air filter Connecting pipe Gas pipe Liquid pipe Drain pipe Sound pressure level High/Med. /Low Under air inlet Back air inlet (mm) (mm) Nominal dia. mm) (dB(A)) (dB(A)) (Pa) 4
3 3
MMD- AP0071SPH (kW) 2. 2/2. 5
AP0091SPH 2. 8/3. 2
AP0121SPH 3. 6/4. 0
AP0151SPH 4. 5/5. 0
AP0181SPH 5. 6/6. 3
1 phase 50Hz 230V (220-240V) (A) (kW) (A) 0. 29 0. 039 0. 51 0. 29 0. 039 0. 51 0. 31 0. 043 0. 54 0. 32 0. 045 0. 56 0. 39 0. 054 0. 68
Zinc hot dipping steel plate (mm) (mm) (mm) (kg) 22 22 210 845 645 22 Fined tube Polyethylene foam + Polyurethane foam Centrifugal fan (Sirocco fan) 540 470/400 600 520/450 60 5 (Factory setting) -15-30-45 4steps 5 Remote controller Standard filter attached (Long life filter) 9. 5 6. 4 25 (Polyvinyl chloride tube : External dia. 32 Internal dia. 25) 36/30 28/24 38/32 29/25 39/33 32/28 40/36 33/29 12. 7 4 (Factory setting) -14-29-44 4steps 6 690 600/520 780 680/580 23 23
Specifications
60Hz
Model name Cooling/Heating capacity Electrical characteristics Power supply Running current Power consumption Starting current Appearance Dimension Height Width Depth Total weight Heat exchanger Soundproof / Heat-insulating material Fan Standard air flow High (Med. /Low) Motor External static pressure (m /h) (m /h) (W) (Pa) 6 (Factory setting) -16-31-46 4steps Air filter pressure loss Controller Air filter Connecting pipe Gas pipe Liquid pipe Drain pipe Sound pressure level Under air inlet High/Med. /Low Back air inlet (mm) (mm) Nominal dia. mm) (dB(A)) (dB(A)) (Pa) 4
3 3
MMD- AP0071SPH (kW) 2. 2/2. 5
AP0091SPH 2. 8/3. 2
AP0121SPH 3. 6/4. 0
AP0151SPH 4. 5/5. 0
AP0181SPH 5. 6/6. 3
1 phase 60Hz 220V (A) (kW) (A) 0. 27 0. 037 0. 47 0. 27 0. 037 0. 47 0. 30 0. 041 0. 53 0. 31 0. 043 0. 54 0. 37 0. 052 0. 65
Zinc hot dipping steel plate (mm) (mm) (mm) (kg) 22 22 210 845 645 22 Fined tube Polyethylene foam + Polyurethane foam Centrifugal fan (Sirocco fan) 540 470/400 600 520/450 60 5 (Factory setting) -15-30-45 4steps 5 Remote controller Standard filter attached (Long life filter) 9. 5 6. 4 25 (Polyvinyl chloride tube : External dia. 32 Internal dia. 25) 36/30 28/24 38/32 29/25 39/33 32/28 40/36 33/29 12. 7 4 (Factory setting) -14-29-44 4steps 6 690 600/520 780 680/580 23 23
Electrical current characteristics
Slim Duct
Type Nominal Voltage (V-Ph-Hz) S-MMS (50Hz) MMD-AP0071SPH MMD-AP0091SPH MMD-AP0121SPH MMD-AP0151SPH MMD-AP0181SPH S-MMS (60Hz) MMD-AP0071SPH MMD-AP0091SPH MMD-AP0121SPH MMD-AP0151SPH MMD-AP0181SPH S-HRM MMD-AP0071SPH MMD-AP0091SPH MMD-AP0121SPH MMD-AP0151SPH MMD-AP0181SPH 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 Voltage Range Min 198 198 198 198 198 198 198 198 198 198 198 198 198 198 198 Max 264 264 264 264 264 264 264 264 264 264 264 264 264 264 264 Fan Motor kW 0. 060 0. 060 0. 060 0. 060 0. 060 0. 060 0. 060 0. 060 0. 060 0. 060 0. 060 0. 060 0. 060 0. 060 0. 060 FLA 0. 35 0. 35 0. 37 0. 38 0. 47 0. 32 0. 32 0. 36 0. 37 0. 44 0. 35 0. 35 0. 37 0. 38 0. 47 Power Supply MCA 0. 44 0. 44 0. 47 0. 48 0. 59 0. 41 0. 41 0. 45 0. 47 0. 56 0. 44 0. 44 0. 47 0. 48 0. 59 MOCP 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
Sensible capacity table
Slim Duct Type ( MMD-AP***SPH )
TC : Total capacity [kW] Unit size Outdoor air temp. [. . . ] Model name MMDAP0071SPH AP0071SH-C Standard air flow (m3/h) 540 AP0091SPH AP0091SH-C 540 AP0121SPH AP0121SH-C 600
AP0071SPH-C AP0091SPH-C AP0121SPH-C
Provide an air filter in fresh air duct. ( Fresh air doesn't pass through the filter of Indoor unit. ) Be sure to insulate the fresh air duct. Please wire for inter - lock with fan of Heat exchanger unit and Indoor unit.
30
Static Pressure (Pa)
20 10 0 -10 0 20 40 60 80 100 120 140
Fresh Air Volume (m3/h)
Indoor unit
Duct fan motor
Fresh Air Volume
Flange Option :TCB-FF101URE
Inter - lock circuit
Connect the driving relay of the duct fan (DC 12V) between 1 and 6 on the indoor P. C. (Rated current of the relay for duct fan shall be up to 75mA. ) After installation, implement a trial operation to check that the duct fan of the indoor unit start/stop simultaneously. (Implement the trial operation following to the installation manual of the indoor unit. )
Fresh air intake (Design guide)
Slim Duct
MMD-AP0151SPH, AP0181SPH MMD-AP0151SPH-C, AP0181SPH-C MMD-AP0151SH-C, AP0181SH-C
Caution
The fresh air shall be treated by heat reclaim ventilator or the like. Be sure to decide the fresh air volume so that mixed suction air with fresh air keep operating temperature *1. Recommended treated air temperature is 12C to 30C. However, please make a fresh air volume within 20% of standard. Model name MMDAP0151SPH AP0151SPH-C AP0151SH-C Standard air flow (m3/h) 690 AP0181SPH AP0181SPH-C AP0181SH-C 780
Provide an air filter in fresh air duct. [. . . ] (Implement the trial operation following to the installation manual of the indoor unit. )
Slim Duct Type Engineering Data Book
TOSHIBA CARRIER CORPORATION
Jun. 2005 [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA MMD-AP0181SPH
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.