INSTALLATION MANUAL
R410A
Heat Recovery Type
Indoor Unit
<4-way Air Discharge Cassette Type>
(2 Series)
Outdoor Unit
<Inverter Unit>
MMU-AP0091H, AP0121H, AP0151H, MMU-AP0181H, AP0241H, AP0271H, MMU-AP0301H, AP0361H, AP0481H MMU-AP0561H
<2-way Air Discharge Cassette Type>
MMY-MAP0802FT8 MMY-MAP1002FT8 MMY-MAP1202FT8
MMU-AP0071WH, AP0091WH, AP0121WH, MMU-AP0151WH, AP0181WH, AP0241WH, MMU-AP0271WH, AP0301WH, AP0481WH*
<1-way Air Discharge Cassette Type>
FS unit
RBM-Y1122FE RBM-Y1802FE RBM-Y2802FE
* CHINA market only
MMU-AP0071YH, AP0091YH, AP0121YH, MMU-AP0151SH, AP0181SH, AP0241SH
<Concealed Duct Standard Type>
MMD-AP0071BH, MMD-AP0151BH, MMD-AP0271BH, MMD-AP0481BH,
AP0091BH, AP0121BH, AP0181BH, AP0241BH, AP0301BH, AP0361BH, AP0561BH
<Concealed Duct High Static Pressure Type>
MMD-AP0181H, AP0241H, AP0271H, MMD-AP0361H, AP0481H, AP0721H, MMD-AP0961H
<Under Ceiling Type>
MMC-AP0151H, AP0181H, AP0241H, MMC-AP0271H, AP0361H, AP0481H
<High Wall Type>
MMK-AP0071H, AP0091H, AP0121H, MMK-AP0151H, AP0181H, AP0241H, MMK-AP0072H*, AP0092H*, AP0122H*
<Floor Standing Cabinet Type>
* European market only
MML-AP0071H, AP0091H, AP0121H, MML-AP0151H, AP0181H, AP0241H
<Floor Standing Concealed Type>
MML-AP0071BH, AP0091BH, AP0121BH, MML-AP0151BH, AP0181BH, AP0241BH
<Floor Standing Type>
MMF-AP0151H, AP0181H, AP0241H MMF-AP0271H, AP0361H, AP0481H MMF-AP0561H
PRINTED IN JAPAN, 2005
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. [. . . ] (Sold separately)
NOTE :
The connecting length indicated in the table represents the length from the pull box to the outdoor unit when the indoor units are connected in parallel for power, as shown in the illustration below. A voltage drop of no more than 2% is also assumed. If the connecting length will exceed the length indicated in the table, select the wire thickness in accordance with indoor wiring standards.
· Group Control through a Remote Controller
Group control of multiple indoor units (8 units) through a single remote controller switch
Indoor unit No. 1
AB
No. 2
AB
No. 3
AB
No. 4
AB
No. 7
AB
No. 8
AB
Remote controller
(A. B)
Indoor power source single phase 220240V, 50Hz
Earth leakage breaker
Switch Pull box
FS unit
FS unit
FS unit
FS unit
FS unit
FS unit
FS unit
FS unit
CAUTION
(1) Keep the refrigerant piping system and the indoor-indoor/indoor-outdoor control wiring systems together. (2) When running power wires and control wires parallel to each other, either run them through separate conduits, or maintain a suitable distance between them. (Current capacity of power wires: 10A or less for 300mm, 50A or less for 500mm)
101
9-5. System Wiring Diagram
Power supply 3 phase 380-415V 50Hz
Power supply 3 phase 380-415V 50Hz
Power supply 3 phase 380-415V 50Hz
Earth leakage breaker Power switch
Earth leakage breaker Power switch
Earth leakage breaker Power switch
Outdoor unit
Earth terminal Earth terminal Earth terminal
Earth
Earth
Earth
Earth
Earth
Earth
U1 U2 terminal U3 U4 U5 U6 terminal
U1 U2 terminal U3 U4 U5 U6 terminal
U1 U2 terminal U3 U4 U5 U6 terminal
U1/U3
Outdoor side
U2/U4
Single phase 220-240V 50Hz Central remote controller
Indoor side
Indoor unit
A
Remote controller
A B
Indoor unit
A
Remote controller
A B
Indoor unit
A
Remote controller
A B
U1/U2
Earth terminal
L N
B
U1/U2
Earth terminal
L N
B
U1/U2
Earth terminal
L N
B
Control wiring
FS unit CN02
Control wiring
FS unit CN02
Control FS unit wiring CN02 Power line CN01 Earth terminal
CN81 Power line Earth terminal
Power line Earth terminal
CN01 Earth terminal
CN01 Earth terminal Earth terminal
Power supply Single phase 220-240V 50Hz Earth leakage breaker Power switch
Pull Box
Pull Box
NOTE :
Control wire and power line wire between FS unit and indoor unit are the accessary parts of FS unit. (Wire length : 6m) If the length between indoor and FS unit exceeds 5m, connect by using the connection cable kit sold separately (RBC-CBK15FE).
102
9-6. Connection of Power Supply Cable with Control Wire
Insert power supply cable and control wire after removing knockout of the piping/wiring panel at front side of the outdoor unit.
Knockout for power supply cable Knockout for control wire Piping/wiring panel
When insert power supply cable and control wire, protect power supply cable and control wire from edge after removing knockout.
Power supply cable
1. Connect the power supply cables and earthing wire to the terminal block of the power supply through a notched section at side of the electric parts box, and fix with a clamp. Bundle the power supply cables using the hole so that they are not out of the notched section of the electric parts box.
Control wire
1. Connect the control wire between indoor and outdoor units and the control wire between outdoor units to (U1, U2, U5, U6) terminal section through a hole at side of the electric parts box, and fix with a clamp. Use the control wire with 2-core shield wire (1. 25mm² or more) in order to prevent noise trouble. (Non-polarity)
NOTE :
1) Be sure to separate the power supply cables and each control cable. 2) Arrange the power supply cables and each control cable so that they do not contact with the bottom surface of the outdoor unit. 3) A terminal block (U3, U4 terminal blocks) for connecting an optional part "Central remote controller etc. " is provided on the inverter unit, so be careful to miswiring.
U1-U6 Terminal U1-U2 : For control wiring between indoor/outdoor unit U3-U4 : For "Central remote controller etc. " U5-U6 : For control wiring between outdoor units
U1 U2 U3 U4 U5 U6
(
)
Earth screw Earth screw L1 Power supply terminal block
L1 L2 L3 N
L2
L3
N
10mm or more
Earth screw
Earth line
Power supply cable
P. C. Electrical Wiring of Flow Selector Unit
Wire connections
Use the supplied, dedicated wires.
REQUIREMENT
· Check that power is not supplied to the indoor unit before connecting wires. · For safety, connect wires to the Flow Selector unit first. · Be sure to put wires through the wire connecting ports on the Flow Selector unit and the indoor unit.
Connection diagram
· Power is supplied from the connected indoor unit. · Connect the attached wires (power supply / control wiring) between the Flow Selector unit and the indoor unit. Connect wires as shown in the below figure. Flow Selector Unit
RBM-Y1802FE Only Earth Screw
Indoor Unit
Attached wire (power supply)
SVD SVS SVS SVSS SVDD
1 1 3 3 1 1 3 3 5 5 7 7 9 9
11
CN01 (RED)
CN10 (WHI)
Control P. C. Bord for indoor unit
33
CN67 (BLK)
COM SVD SVS SVDD SVSS
BRW BLU YEL WHI ORN
Control P. C. [. . . ] sensor miscabling (TE, TL) Outdoor pressure sensor miscabling (Pd, Ps) Ps sensor error Pd sensor error Indoor other error Indoor EEPROM error Compressor break down Compressor trouble (lock) Magnet switch error Overcurrent relay operation Current detect circuit system error Comp 1 case thermo operation Low pressure protective operation Oil level down detective protection
Indoor Indoor Indoor I/F I/F I/F I/F I/F Indoor I/F IPDU I/F I/F I/F I/F Indoor I/F IPDU IPDU MG-SW Overcurrent relay IPDU I/F I/F I/F
H02
H02
1d
H03 H04 H06 H07
H03 H04 H06 H07
17 44 20 d7 d4
H08
H08
Oil level detective temp sensor error
I/F
H14
H14
44
Comp 2 case thermo operation Oil level detective circuit error Magnet switch error Overcurrent relay operation
I/F I/F MG-SW Overcurrent relay Indoor I/F I/F
H16
H16
d7
L03 L04 L05
-- L04 --
96 96 96
¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤
--
¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤
SIM SIM SIM
Indoor center unit duplicated Outdoor line address duplicated Duplicated indoor units with priority (Displayed in indoor unit with priority) Duplicated indoor units with priority (Displayed in unit other than indoor unit with priority) Group line in individual indoor unit Indoor group/Address unset Indoor capacity unset Outdoor capacity unset Flow selector unit error Duplicated central control addresses
L06 L07 L08 L09 L10 L18 L20
L06 -- L08 -- L10 L18 L20
No. of indoor units with priority -- -- -- -- -- -- 01: IPDU1 error 02: IPDU2 error 03: IPDU3 error 04: Fan IPDU error 05: IPDU1 + Fan IPDU error 06: IPDU2 + Fan IPDU error 07: All IPDU error Detected indoor address --
96 99 99 46 88 8A 98
SIM SIM SIM SIM SIM SIM SIM
I/F Indoor Indoor, I/F Indoor I/F I/F AI-NET, Indoor
L29
L29
CF
SIM
No. of IPDU error
I/F
L30 --
L30 L31
b6 --
SIM
Indoor outside interlock Extended I/C error
Indoor I/F
182
Check code Main remote controller display P01 P03 P04 P05 P07 P10 P12 P13 P15 P17 P19 P20 -- P03 P04 P05 P07 P10 -- P13 P15 P17 P19 P20 0 1 P22 P22 3 C D P26 P29 P31 -- -- -- P26 P29 P31 -- -- -- Outdoor 7-segment display Auxiliary code -- -- 01: Comp. 2 side 01: Phase-missing detection 02: Phase error 01: Comp. [. . . ]