If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TOSHIBA RAS-13UKP-ES. We hope that this TOSHIBA RAS-13UKP-ES user guide will be useful to you.
Lastmanuals help download the user guide TOSHIBA RAS-13UKP-ES.
Manual abstract: user guide TOSHIBA RAS-13UKP-ESSERVICE MANUAL
Detailed instructions for use are in the User's Guide.
[. . . ] SVM-02005(1)
SERVICE MANUAL
AIR-CONDITIONER
SPLIT WALL TYPE
RAS-13UKP-ES / RAS-13UA-ES RAS-10UKP-ES / RAS-10UA-ES RAS-07UKP-ES / RAS-07UA-ES
07 Class
10/13 Class
Revised on May, 2002
FILE NO. CONSTRUCTION VIEWS
2-1 Indoor Unit 2-2 Outdoor Unit (RAS-13UA-ES) 2-3. SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit 4-2 Outdoor Unit (RAS-13UA-ES) 4-3 Outdoor Unit (RAS-10UA-ES, RAS-07UA-ES)
5. REFRIGERATION CYCLE DIAGRAM
5-1 RAS-13UKP-ES / RAS-13UA-ES 5-2 RAS-10UKP-ES / RAS-10UA-ES 5-3 RAS-07UKP-ES / RAS-07UA-ES
6. [. . . ] Cut the pipe with a pipe cutter.
Obliquity Roughness Warp
(Unit : N·m) Outer dia. of copper pipe 6. 35 mm 9. 52 mm Tightening torque 16 to 18 (1. 6 to 1. 8 kgf·m) 33 to 42 (3. 3 to 4. 2 kgf·m)
90°
Fig. Insert a flare nut into the pipe, and flare the pipe. · Projection margin in flaring : A (Unit : mm)
A
· Tightening torque of flare pipe connections The operating pressure of R-410A is higher than that of R-22. It is therefore necessary to firmly tighten the flare pipe connecting sections (which connect the indoor and outdoor units) up to the specified tightening torque. Incorrect connections may cause not only a gas leakage, but also damage to the refrigerant cycle.
Flare at indoor unit side
Die
Pipe
Fig. of copper pipe 6. 35 9. 52 R-410A tool used 0 to 0. 5 0 to 0. 5 Conventional tool used 1. 0 to 1. 5 1. 0 to 1. 5
Flare at outdoor unit side
Fig. 8-5-4 Imperial (wing nut type, conventional tool) Outer dia. of copper pipe 6. 35 9. 52 <Tightening connection> Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.
Half union
R-410A
85
mm
1. 5 to 2. 0 1. 5 to 2. 0
Mark line
For RAS-07UA-ES
Fig. 8-5-5
Flare nut
CAUTION
· Do not apply excess torque. · Otherwise, the nut may crack depending on the conditions.
Externally threaded side
Internally threaded side
Use a wrench to secure.
Use a torque wrench to tighten.
Fig. 8-5-6
CAUTION
· KEEP IMPORTANT 4 POINTS FOR PIPING WORK (1) Take away dust and moisture (Inside of the connecting pipes. ) (2) Tight connection (between pipes and unit) (3) Evacuate the air in the connecting pipes using VACUUM PUMP. (4) Check gas leak (connected points) 35
FILE NO. Evacuating After the piping has been connected to the indoor unit, you can perform the air purge together at once. AIR PURGE Evacuate the air in the connecting pipes and in the indoor unit using a vacuum pump. Do not use the refrigerant in the outdoor unit. For details, see the manual of the vacuum pump. <Using a vacuum pump> Be sure to use a vacuum pump with counter-flow prevention function so that inside oil of the pump does not flow backward into pipes of the air conditioner when the pump stops. (If oil inside of the vacuum pump enters into the air conditioner, which use R-410A, refrigeration cycle trouble may result. ) 1. Connect the charge hose from the manifold valve to the service port of the gas side packed valve. Connect the charge hose to the port of the vacuum pump. [. . . ] (7-Screws 4 x 10L with nylon washer) Pull the front lower portion toward you, and remove it pulling out upward. Remarks
Remove 7-Screws 4 x 10L
2-Screws 4 x 10L
2-Screws 4 x 22L
2
Capacitor for compressor
1) Perform the common procedure 1. 2) Remove the fixing screw and the capacitor band. (1-Screw 4 x 8L) 3) Disconnect the lead wires. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA RAS-13UKP-ES
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.