Manual abstract: user guide TOSHIBA RAS-16SAV-ESERVICE MANUAL
Detailed instructions for use are in the User's Guide.
[. . . ] SVM-07036-1
SERVICE MANUAL
SPLIT TYPE
Indoor Unit
<High Wall, Heat Pump Type>
Outdoor Unit
<Heat Pump Type>
RAS-13SKV-E RAS-16SKV-E RAS-10SKVR-E RAS-13SKVR-E RAS-16SKVR-E
RAS-13SAV-E RAS-16SAV-E RAS-10SAVR-E RAS-13SAVR-E RAS-16SAVR-E
R410A
Revised March, 2007
CONTENTS
1. SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REFRIGERANT R410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] Open the air inlet grille upward and pull it toward you. Remove the terminal cover and cord clamp. Insert the connecting cable (or as according to local regulations/codes) into the pipe hole on the wall. Pull the connecting cable through the cable slot on the rear panel so that it protrudes about 15 cm out of the front. Insert the connecting cable fully into the terminal block and secure it tightly with screws. Tightening torque: 1. 2 N·m (0. 12 kgf·m) 7. Secure the connecting cable with the cord clamp. Attach the terminal cover, rear plate bushing and air inlet grille on the indoor unit.
60
Revised-1
CAUTION
· Be sure to refer to the wiring system diagram labeled inside the front panel. · Check local electrical regulations for any specific wiring instructions or limitations.
10-3-5. Piping and Drain Hose Installation Piping and drain hose forming
· Since condensation results in machine trouble, make sure to insulate both the connecting pipes separately. (Use polyethylene foam as insulating material. )
Rear right
Terminal cover Screw
1
2
3
Left Bottom right
Earth line
Right
Screw
Fig. Die-cutting front panel slit Cut out the slit on the left or right side of the front panel for the left or right connection and the slit on the bottom left or side of thefront panel for the bottom left or right connection with a pair of nippers. Changing drain hose For left connection, left-bottom connection and rear-left connection's piping, it is necessary to relocate the drain hose and drain cap.
1
2
3
Fig. 10-3-7
How to remove the drain cap
Clip drain cap with needle-nose pliers, and pull out.
Connecting cable
abou
t 15
cm
Fig. 10-3-8
110 mm
10 mm
How to remove the drain hose
The drain hose is secured in place by a screw. Remove the screw securing the drain hose, then pull out the drain hose.
10 mm
50 mm
Fig. 10-3-9
NOTE : WIRE TYPE : more than 1. 0mm2. (H07 RN-F or 60245 IEC 66).
Screw
Fig. 10-3-12
61
Die-cutting Front panel slit
Bottom left
Drain hose
Changing drain hose
Terminal block
Rear left
Piping preparation
Cord clamp
How to attach the drain cap
1. Insert hexagonal wrench (4 mm).
In case of bottom right or bottom left piping
· After making slits on the front panel with a knife or similar tool, cut them out with a pair of nippers or an equivalent tool.
Slit
4 mm
Fig. 10-3-13
Left-hand connection with piping
2. Bend the connecting pipes so that they are positioned within 43 mm above the wall surface. If the connecting pipes are positioned more than 43 mm above the wall surface, the indoor unit may be unstable. [. . . ] Refer to the figure shown on the left.
13
TD sensor (Discharge pipe temperature sensor) · Attachment With its leads pointed upward, install the sensor onto the vertical straight pipe part of the discharge pipe.
14
TO sensor (Outside air temperature sensor) · Attachment Insert the outdoor air temperature sensor into the holder, and install the holder onto the heat exchanger.
Detail A TS sensor
Detail B TD sensor
Arrow D TO sensor
TO sensor holder
CAUTION During the installation work (and on its completion), take care not to damage the coverings of the sensor leads on the edges of the metal plates or other parts. It is dangerous for these coverings to be damaged since damage may cause electric shocks and/or a fire. CAUTION After replacing the parts, check whether the positions where the sensors were installed are the proper positions as instructed. The product will not be controlled properly and trouble will result if the sensors have not been installed in their proper positions.
113
No.
15
Part name Replacement of temperature sensor for servicing only Common service parts of sensor TO, TS, TE, TD
Procedure 1) Cut the sensor 100 mm longer than old one. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA RAS-16SAV-E
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.