User manual TOSHIBA RAS-24SKHP-ES SERVICE MANUAL

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TOSHIBA RAS-24SKHP-ES. We hope that this TOSHIBA RAS-24SKHP-ES user guide will be useful to you.

Lastmanuals help download the user guide TOSHIBA RAS-24SKHP-ES.


Mode d'emploi TOSHIBA RAS-24SKHP-ES
Download
Manual abstract: user guide TOSHIBA RAS-24SKHP-ESSERVICE MANUAL

Detailed instructions for use are in the User's Guide.

[. . . ] SVM-09036 SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-18SKHP-ES / RAS-18S2AH-ES RAS-24SKHP-ES / RAS-24S2AH-ES RAS-18SKP-ES / RAS-18SA-ES RAS-24SKP-ES / RAS-24SA-ES February, 2009 FILE NO. SPECIFICATIONS CONSTRUCTION VIEWS 2-1 2-2 Indoor Unit Outdoor Unit 3. WIRING DIAGRAM 3-1 RAS-18SKP-ES / RAS-18SA-ES, RAS-24SKP-ES / RAS-24SA-ES 3-2 RAS-18SKHP-ES / RAS-18S2AH-ES RAS-24SKHP-ES / RAS-24S2AH-ES 4. SPECIFICATION OF ELECTRICAL PARTS 4-1 4-2 4-3 4-4 4-5 4-6 Indoor Unit (RAS-18SKP-ES, RAS-24SKP-ES) Outdoor Unit (RAS-18SA-ES) Outdoor Unit (RAS-24SA-ES) Indoor Unit (RAS-18SKHP-ES, RASP-24SKHP-ES) Outdoor Unit (RAS-18S2AH-ES) Outdoor Unit (RAS-24S2AH-ES) 5. REFRIGERATION CYCLE DIAGRAM 5-1 5-2 5-3 5-4 RAS-18SKP-ES / RAS-18SA-ES RAS-24SKP-ES / RAS-24SA-ES RAS-18SKHP-ES / RAS-18S2AH-ES RAS-24SKHP-ES / RAS-24S2AH-ES 6. CONTROL BLOCK DIAGRAM 6-1 RAS-18SKP-ES / RAS-18SA-ES, RAS-24SKP-ES / RAS-24SA-ES 6-2 RAS-18SKHP-ES / RAS-18S2AH-ES RAS-24SKHP-ES / RAS-24S2AH-ES ­1­ FILE NO. SVM-09036 7. OPERATION DESCRIPTION 7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10 7-11 7-12 Remote control Outline of Air Conditioner Control Description of Operation Circuit Description of Safety and Reliability Prevention Function One-Touch Operation Hi POWER Operation QUIET Operation ECO Operation COMFORT SLEEP Operation FILTER Check lamp Auto Restart Function Self-Cleaning Operation Safety Cautions Installation Diagram of Indoor and Outdoor Units Installation Indoor Unit Outdoor Unit Test Operation Troubleshooting Procedure Basic Check Items Primary Judgement Self-Diagnosis by Remote Control (Check Code) How To Diagnose Faulty Parts Troubleshooting for Indoor unit Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire) Troubleshooting for P. C. Board Troubleshooting for Remote Control 8. INSTALLATION PROCEDURE 8-1 8-2 8-3 8-4 8-5 8-6 9. TROUBLESHOOTING CHART 9-1 9-2 9-3 9-4 9-5 9-6 9-7 9-8 9-9 10. [. . . ] of copper pipe 6. 35 12. 70 R410A 1. 5 to 2. 0 2. 0 to 2. 5 <Tightening connection> Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure. Strong wind CAUTION · Do not apply excess torque. · Otherwise, the nut may crack depending on the conditions. Fig. Evacuating After the piping has been connected to the indoor unit, you can perform the air purge together at once. AIR PURGE Evacuate the air in the connecting pipes and in the indoor unit using a vacuum pump. Do not use the refrigerant in the outdoor unit. For details, see the manual of the vacuum pump. <Using a vacuum pump> Be sure to use a vacuum pump with counter-flow prevention function so that inside oil of the pump does not flow backward into pipes of the air conditioner when the pump stops. (If oil inside of the vacuum pump enters into the air conditioner, which use R410A, refrigeration cycle trouble may result. ) 1. Connect the charge hose from the manifold valve to the service port of the gas side packed valve. Connect the charge hose to the port of the vacuum pump. Open fully the low pressure side handle of the gauge manifold valve. Operate the vacuum pump to start evacuating. Perform evacuating for about 15 minutes if the piping length is 20 meters. (15 minutes for 20 meters) (assuming a pump capacity of 27 liters per minute. Then confirm that the compound pressure gauge reading is ­101 kPa (­76 cmHg). Close the low pressure side valve handle of gauge manifold. Open fully the valve stem of the packed valves (both side of Gas and Liquid). Remove the charging hose from the service port. Securely tighten the caps on the packed valves. Outer dia. of copper pipe 6. 35 mm 12. 70 mm Tightening torque 16 to 18 (1. 6 to 1. 8 kgf·m) 50 to 62 (5. 0 to 6. 2 kgf·m) · Tightening torque of flare pipe connections The operating pressure of R410A is higher than that of R22. It is therefore necessary to firmly tighten the flare pipe connecting sections (which connect the indoor and outdoor units) up to the specified tightening torque. [. . . ] 1) Perform the common procedure 1 2) Remove the fixing screw. (1 screw 4 x 10L) 3) Disconnect the lead wires from the capacitor terminal. 1) Perform the common procedure 1 2) Remove the fixing screw. (2 screws 4 x 18L) 3) Disconnect the lead wires from the terminal. [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA RAS-24SKHP-ES

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets...
In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.

Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual TOSHIBA RAS-24SKHP-ES will begin.

Search for a user manual

 

Copyright © 2015 - LastManuals - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.

flag