If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TOSHIBA RAV-SM563AT-E. We hope that this TOSHIBA RAV-SM563AT-E user guide will be useful to you.
Lastmanuals help download the user guide TOSHIBA RAV-SM563AT-E.
You may also download the following manuals related to this product:
TOSHIBA RAV-SM563AT-E DATA BOOK (1949 ko)
Manual abstract: user guide TOSHIBA RAV-SM563AT-ESERVICE MANUAL
Detailed instructions for use are in the User's Guide.
[. . . ] 2007
SERVICE MANUAL/INTEGRATION
AIR-CONDITIONER
SPLIT TYPE
INDOOR UNIT
<DIGITAL INVERTER> RAV-SM563UT-E RAV-SM562BT-E RAV-SM803UT-E RAV-SM802BT-E RAV-SM1103UT-E RAV-SM1102BT-E RAV-SM1403UT-E RAV-SM1402BT-E <SUPER DIGITAL INVERTER> RAV-SP1102UT-E RAV-SM562CT-E RAV-SM802CT-E RAV-SM1102CT-E RAV-SM1402CT-E
OUTDOOR UNIT
<DIGITAL INVERTER> RAV-SM563AT-E RAV-SM803AT-E RAV-SM1103AT-E RAV-SM1403AT-E <SUPER DIGITAL INVERTER> RAV-SP562AT-E RAV-SP802AT-E RAV-SP1102AT-E RAV-SP1402AT-E
R410A
PRINTED IN JAPAN, Mar. , 2007 ToMo
ADOPTION OF NEW REFRIGERANT
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. The cleaning diagram for the air filter is there for the service person, and not for the customer.
NOTE
A direct current motor is adopted for indoor fan motor in the Concealed Duct Standard Type air conditioner. Caused from its characteristics, a current limit works on the direct current motor. When replacing the highperformance filter or when opening the service board, be sure to stop the fan. [. . . ] 2007
[L29 error]
Are connections of CDB CN800 and CDB IPDU CN06 connectors normal?YES Was the error just after power ON determined?NO
NO
Correct connection of connector.
YES Are cabling/connector normal?YES
NO
Check cabling between IPDU and CDB and connector.
IPDU P. C. board error Defect Replace
®
YES Is there no abnormal overload?board come to closely contact with heat sink?YES NO
Improve and eliminate the cause.
Correct mounting.
IPDU P. C. board error Defect Replace
®
[H02 error]
NO Is power voltage normal?YES Are connections of cable/connector normal?YES Does electron expansion valve normally operate?YES NO NO NO
Improve power line.
Check and correct circuit cabling such as cabling to compressor (phase missing) and connector.
Compressor lock
® Replace ® ®
Check TE and TS sensors. Defect Replace
®
* For RAV-SM563AT-E, SM803AT-E, replace control P. C. board.
96
Revised : Mar. 2007
[P03 error]
Is protective control such as discharge temprelease control normal?YES
NO
Are connections of cable/connector normal?YES
NO
Correct the cabling and connection of connector.
Check parts. Defect
® Replace
NO Is charged refrigerant amount normal?NO Are characteristics of TD sensor resistance value normal?YES NO * Refer to Characteristics-4.
Check and correct the charged refrigerant amount.
Improve and delete the cause
Replace TD sensor.
Check CDB. Defect Replace * For RAV-SM563AT-E, SM803AT-E, replace control P. C. board.
®
[H01 error]
Is power voltage normal?YES
NO
Improve power line.
YES Is not abnormal overload? [. . . ] Do not put the heating part near the electric parts box. Perform cable process for collected cord heater and fan motor lead cables.
After incorporating the inverter assembly as before, furthermore perform cable process for cord heater and power cord. For the cord heater, perform cable process so that there is no looseness or sag at the fan side. Perform cable process for the cord heater together with the fan motor lead cable, and collect the remained part of cables at cable process part of the inverter.
3-3
P-shape clamp
Secure the power cord for the cord heater to the terminal block mounting plate using the P-shape clamp, and pull it out from the wiring area of the side cabinet (R). [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA RAV-SM563AT-E
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.