If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TOSHIBA RAV-SM802KRT-E. We hope that this TOSHIBA RAV-SM802KRT-E user guide will be useful to you.
Lastmanuals help download the user guide TOSHIBA RAV-SM802KRT-E.
You may also download the following manuals related to this product:
TOSHIBA RAV-SM802KRT-E PSD (7 ko)
Manual abstract: user guide TOSHIBA RAV-SM802KRT-ESERVICE MANUAL
Detailed instructions for use are in the User's Guide.
[. . . ] FILE NO. SVM-05053
SERVICE MANUAL
HI WALL TYPE (INDOOR UNIT)
RAV-SM562KRT-E RAV-SM802KRT-E
R410A
October, 2005
CONTENTS
1. SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CONSTRUCTION VIEWS (EXTERNAL VIEWS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SYSTEMATIC REFRIGERATING CYCLE DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] Lost-phase operation of power supply (3-phase models) 1. Lost-phase operation of power supply Check 3-phase power voltages and wiring. Freezing cycle overload operation
H02
H03
Indicated when an error is detected
H06*1
OFF
Indicated when an error is detected
L29
OFF
Indicated when an error is detected
L31*1
Operation continued (compressor OFF) OFF
Indicated when an error is detected
1. Check phase sequence, reverse phase, and phase loss. Check high-pressure switch circuit wiring. Failure of electronic expansion valve 3. Overcurrent protection circuit operation of outdoor unit fan driver 3. The circuit is activated even after compressor's 3P connector is disconnected. Check outdoor unit CDB board.
P03
Abnormal discharge temperature (over specified value)
Indicated when an error is detected Indicated when an error is detected
P04
P22
Failure of high-pressure protection circuit OFF (Temperature over specified value detected by TE sensor) High-pressure switch (normal models) OFF Failure of outdoor unit DC fan
Indicated when an error is detected
P26
P29
OFF Inverter overcurrent protection circuit activated (short time) Main circuit short voltage operation OFF Failure of IPDU position detect circuit Improper mounting, disconnection OFF or short-circuit of outdoor unit temp. sensor TD Improper mounting, disconnection OFF or short-circuit of outdoor unit temp. sensor TE, TS Improper mounting, disconnection or short-circuit of outdoor unit outside air temp. sensor TO Operation continued
Indicated when an error is detected Indicated when an error is detected Indicated when an error is detected Indicated when an error is detected Indicated when an error is detected
F04
F06
F08
*1 ROA-P*** is not detected by 1HS models. Fan continues rotating in a failure mode detected by outdoor unit because there is no communication between outdoor unit and follower indoor unit in twin group.
34
Troubleshooting (Continued)
2. Troubleshooting by Remote Controller Check Indication
Main Remote Controller (RBC-AMT31E) (1) Checking
When an error occurs in the air conditioner, a check code and an indoor unit number appear on the LCD of remote controller. Check code is displayed only during operation. If indication disappears, check errors following "Checking Error Log" below.
Check code
Faulty indoor unit No.
(2) Checking Error Log
When an error occurs in the air conditioner, error log can be checked following the steps below. Error log can be checked in both operation ON and OFF states.
Step Operation Press [SET] and [TEST] at the same time for 4 seconds or more. The LCD indication changes as shown below. Indication of "SERVICE CHECK" shows that the unit is in the error log mode. "01" (order of error log) is displayed. · The address of faulty indoor unit is displayed in the UNIT No. / buttons displays stored error log sequentially. [. . . ] with buttons.
4
I/U I/U I/U I/U I/U
Refrigerant line address 1 Indoor unit address 1 Group address 1
1 2 2
1 3 2
2 1 2
2 2 2
Indoor unit 5 Set code address
6
For systems like this example, connect a wired remote controller independently without connecting R/C wires, and then set these addresses. Group address Individual: 0000 Header unit: 0001 Follower unit: 0002
Set indoor unit addresses with buttons. Press Indication on the LCD shows normal operation. with buttons.
in case of group control
7
Group 8 Set code address
9
Set indoor unit addresses with buttons as follows: Individual= , header unit= follower unit=
,
8
5
2
4 7 10
3
6
9
10
Press Indication on the LCD shows normal operation. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA RAV-SM802KRT-E
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.