User manual TOSHIBA RBC-FDP2-BMS-PE INSTALLATION MANUAL
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TOSHIBA RBC-FDP2-BMS-PE. We hope that this TOSHIBA RBC-FDP2-BMS-PE user guide will be useful to you.
Lastmanuals help download the user guide TOSHIBA RBC-FDP2-BMS-PE.
Manual abstract: user guide TOSHIBA RBC-FDP2-BMS-PEINSTALLATION MANUAL
Detailed instructions for use are in the User's Guide.
[. . . ] If an input is left unconnected then the corresponding setting will remain at a preset value.
Fault
Ø 4. 00
S1 S2 S3 S4 S5 S6
Setpoint Fanspeed Mode Louvre On/Off Local unlock
No Fault
20. 00 72. 00
Ø 9. 00
FDP2-BMS Control Interface
TCC-NET D-BUS RELAY
S1 to S6 cables should be 0. 5 to 1. 0 mm2 multi-stranded screened twisted pair. The screen should be earthed at one end only. [. . . ] The FDP2 has a number of standard configurations that can be set using switches SW1 to SW7.
LED Functionality
Normal Operation
R G
Key: OFF FLASHING ON
Each control input has a defined control range under voltage and resistance mode as outlined in the following tables. Default settings are applied if the input remains unconnected. These are indicated in the table by the symbol .
S1 Setpoint
Resistance
/Ohms <=0. 4k 1. 3k 2. 1k 2. 9k 3. 8k 4. 6k 5. 4k 6. 3k 7. 1k 7. 9k 8. 8k 9. 6k >200k
Voltage V 1. 4 2. 1 2. 9 3. 6 4. 4 5. 1 5. 9 6. 6 7. 4 8. 1 8. 9 >=9. 6 <1. 0
S2 Fanspeed AUTO HIGH MED LOW LOW Default AUTO
S3 Mode HEAT COOL FAN DRY AUTO AUTO
Resistance
/Ohms <=1k 2. 2k 3. 3k 4. 7k 6. 8k >200k
Voltage V 1. 75 3. 25 4. 75 6. 25 >=7. 75 <1. 0
Power-Up sequence Factory Configuration Power-Up sequence Custom Configuration
R G
R G
No Fault State
18 19 20 21 22 23 24 25 26 27 28 29
R G
R G
Unit Fault
TCC-NET Holdoff. After power-up and during unit configuration
Error Conditions
R G
S4 Louvre OFF ON
S5 On/Off OFF ON
S6 Local LOCK UNLOCK
Resistance
/Ohms >=10k <1k
Voltage V <3. 5 >6. 5
Device configuration error
Default 21
R G
No unit master found on TCC-Net Resistances should be within +/-250 ohms of the quoted value. Voltages should be within +/- 0. 25V of the quoted value. Under open circuit conditions the input will revert to its default value. S1 in resistance mode is designed to be operated using a linear 10k variable resistance.
R G
R
Warnings and Cautions
Do not exceed the specified fault relay ratings
G
D-BUS Communications timeout
Duplicate D-BUS Address detected
It is recommended that volt-free contacts or switch mechanisms connected to S4, S5 and S6 have gold plated contacts to ensure a low resistance circuit when the switch is made.
FDP2-BMS Advanced Operation
ADDRESSING The FDP2 has the facility to create control groups using multiple FDP2s connected together on the D-Bus network. In standard configuration up to 16 FDP2 devices can be connected together. Each FDP2 is assigned a D-Bus address using the configuration switches SW4 to SW7. Unit addresses are shown below.
ADDRESS 0 ADDRESS 4 ADDRESS 8 ADDRESS 12
FDP2-BMS Group Control
Connecting additional FDP2-BMS or FDP2-F controllers as slaves allows larger groups of units to be controlled from the master. With S6 open (LOCKED) units operate to the settings S1 to S5 from the FDP2-BMS master.
S6
FDP2-BMS Slave Input Control
With no inputs connected the FDP2-BMS slave will duplicate the settings of the FDP2 master. If one or more slave inputs S1 to S6 are connected then each input on the slave will override the corresponding value sent from the master. [. . . ] Local Restore operation is shown in the following figure.
18
ADDRESS 0
ADDRESS 1
TCC-NET
D-BUS
RELAY
TCC-NET
D-BUS
RELAY
A
B D1 D2 C R1 R2
A
B D1 D2 C R1 R2
Address 0 (MASTER)
LOCAL CENTRAL Save User Settings CENTRAL CONTROL Use FDP2 Settings CENTRAL LOCAL Restore User Settings
D1 D2 C
D1 D2 C
8 Units max
Functional Specification
SPECIFICATION Use solid or stranded 24awg shielded or unshielded twisted pair to Cat3, Cat4 or Cat5 specification. Use a twisted pair for connections D1, D2 and an extra core for connection C.
D-BUS Address 1-15 (SLAVE)
Electrical
Supply Power Relay
16 FDP2 max
Environmental
18V DC from TCC-NET <1VA 1A, 24VAC max 1A, 30VDC max Temperature Storage Operation Humidity -10oC to 50oC 0oC to 50oC 0-90% RH non-condensing IP30 EN61000-6-1 EN61000-6-3
NETWORK LENGTH Standard installation for total network distances of up to 500m can be achieved following the basic daisy-chaining method showed in the above diagram. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA RBC-FDP2-BMS-PE
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual TOSHIBA RBC-FDP2-BMS-PE will begin.