If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TOSHIBA SATELLITE 5200-904. We hope that this TOSHIBA SATELLITE 5200-904 user guide will be useful to you.
Lastmanuals help download the user guide TOSHIBA SATELLITE 5200-904.
Manual abstract: user guide TOSHIBA SATELLITE 5200-904
Detailed instructions for use are in the User's Guide.
[. . . ] Shared battery system: A parallel UPS system in which there is a single battery for all UPS units in the system. HS: Vent type stand-alone lead storage battery AHH: Sintered electrode type alkaline storage battery MSE: Sealed stand-alone lead storage battery Individual battery system:
(4) Display
Graphic display panel: LCD: LED: Scroll buttons: Includes push buttons, display lamps, and the LCD panel used to display UPS operating procedures and the UPS state. This shows the operational procedure and the status of the UPS unit. Individual lamps located on the graphic display panel indicate the status of the UPS unit. [. . . ] The operator can switch between these screens by pressing the scroll keys.
: Scroll up : Scroll down
Normal Display screen
Failure Data Display screen
Warning Data Display screen
- 20 -
6F3H1001 7. 2. 1 Normal Display Screen
The Normal Display screen indicates the operational status of the UPS and provides a total of nine screens: one Operation Guidance Display screen and eight Measurement Value Display screens. Table 7. 2 presents examples of these screens.
Table 7. 2 No. 1 LCD Screen Help screen (Example 1) Operation status
OPERATION GUIDANCE
MOVE #52R TO "ON" POSITION
Normal Display Screen Description Shows the status of the UPS at the top and help messages or measurements underneath. (Example 1)Shows help messages when starting or stopping operation.
(Example 2)
UPS SUPPLY
(Example 2)Shows the output voltage and output current during operation. 200[V] 50[%] Voltage (example) Current ratio (example)
AC-VO AC- I O
2
Measurement screen (Example) Output voltage
O/P VOLTAGE (LINE)
Shows the output voltage between lines.
U- V V-W W- U 3
200[V] 200[V] 200[V] Shows the RMS value for the output current for each phase as a proportion (%) of the rated value.
Measurement screen (Example) Output current (RMS
value) O/P CURRENT (r. m. s)
U V W
50[%] 50[%] 50[%]
4
Measurement screen (Example) Output current (peak)
O/P CURRENT (PEAK)
Shows the peak value for the output current for each phase as a proportion (%) of the rated value. Peak value for actual output current × 100 [%] TMRS value for rated current × 1. 41
U V W
50[%] 50[%] 50[%]
- 21 -
6F3H1001
Table 7. 2 5 Measurement screen (Example) Output frequency O/P FREQUENCY FREQ. 60. 0[Hz] Normal Display Screen (continued) Shows the output frequency.
6
Measurement screen (Example) AC input AC INPUT AC I/P-V 200[V] FREQ. 60. 0[Hz]
Shows the frequency and voltage values for AC input.
7
Measurement screen (Example) Bypass input BYPASS INPUT BYP I/P-V 200[V] FREQ. 60. 0[Hz]
Shows the frequency and voltage values for bypass input.
8
Measurement screen (Example) DC value DC INPUT DC-V BATT-V BATT- I 401[V] 401[V] 0[A]
Shows the DC voltage and DC current. For the current value, "-" indicates charging and the absence of a plus/minus sign indicates discharging.
9
Measurement screen (Example) Counter value MODE COUNT UPS 17544[H] BATTERY 32[MIN] 0[TIM]
Shows the total time of UPS operation and the number of times the battery has been operated and total time for battery use (the time AC input has been off).
- 22 -
6F3H1001 7. 2. 2 Failure Display Screen
The Failure Display screen indicates the presence or absence of failure data and displays that data if present.
Table 7. 3 LCD Screen Presence or absence of failure data FAULT NO FAULT INFORMATION Failure Display Screen Description This screen indicates the presence or absence of failure data. This screen is displayed if there is no failure data, or if all failure data has been reset with the "fault display rest" key.
Failure data FAULT 1 52R TRIP 98-09-09 08:05:30 ANOTHER ITEM
The failure data, the time the failure occurred, and an indication as to whether or not there is any other failure data is displayed with this screen if a failure occurs. Turns off the control power supply and shuts down the UPS completely. Changes the mode for battery charging (in the case of HS or AHH individual battery). Used to change the charging mode manually from protective charge to floating charge (in the case of an MSE individual battery). Changes the supply of power to the load to bypass power supply (when the UPS must be shut down completely for maintenance, inspection, etc. ).
7
Supply power to maintenance bypass
Page 39
8. 2 Pre-operational check
Be sure to check the following items before operating the UPS: (1) Make sure all internal covers are in place. If doors are opened to operate circuit breakers, switches and the like, be sure to close them afterward. (3) Make sure the air conditioners in the UPS chamber and battery chamber are operating. (4) When starting up the UPS, make sure all circuit breakers (52R, 72B, 52C, 52L and 52M) and switches (8A and 6CH) are off. (Certain systems are also provided with the switch 8D. ) (5) When starting up the UPS, check on the equipment supplying power to the UPS to make sure AC input voltage is being supplied to the UPS.
- 26 -
6F3H1001
8. 3 Procedures
8. 3. 1 Startup
Table 8. 1 shows the procedure used to start up the UPS. LED status : Unlit : Lit
Table 8. 1 Step 1 Procedure Turn on the control power supply switch (8A) on the panel.
: Blinking
Startup Procedures
LCD/LED Status (After Execution)
OPERATION GUIDANCE
MOVE #52C AND #52L TO `ON' POSITION
AC INPUT
CONVERTER
INVERTER
UPS
FLOAT CHARGE BATTERIES EQUAL CHARGE DISCHARGE
AC SWITCH
AC OUTPUT
BYPASS INPUT
BYPASS
The "BYPASS" LED lit. 2 Turn on the bypass AC input 52C and the AC output 52L circuit breakers. (The UPS will change to bypass power supply status and AC output voltage will be generated. )
AC INPUT
BYPASS MOVE #6CH TO `ON' POSITION
CONVERTER
INVERTER
UPS
FLOAT CHARGE BATTERIES EQUAL CHARGE DISCHARGE
AC SWITCH
AC OUTPUT
BYPASS
BYPASS INPUT
The "BYPASS INPUT" and The "OUTPUT"LEDs lit. [. . . ] Figure 9. 9 Changing Screens with Scroll Keys
- 49 -
6F3H1001
9. 3 Saving Waveforms
When the unit has stopped due to failure, be sure to remove the memory card before resetting the LCD Failure Error screen on the panel, so you can give it to the service person. Resetting (restarting) the UPS without removing the memory card will delete the data needed to determine the cause of the failure. Every effort has been made to ensure safety in unit handling. However, when removing the memory card, do not touch the other sections of the unit. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA SATELLITE 5200-904
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.