[. . . ] 6F3B0253 UM-TS01-E031
PROGRAMMABLE CONTROLLER
PROSEC
T1- 16S
USER'S MANUAL - Basic Hardware and Function -
TOSHIBA CORPORATION
6F3B0253
Important Information
Misuse of this equipment can result in property damage or human injury. Because controlled system applications vary widely, you should satisfy yourself as to the acceptability of this equipment for your intended purpose. In no event will Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the use of this equipment. No patent liability is assumed by Toshiba Corporation with respect to use of information, illustrations, circuits, equipment or examples of application in this publication. [. . . ] Refer to Note of Shift register FUN 074. · Multiple counter instructions (CNT) with
132
T1-16S User's Manual
6F3B0253
7. Instructions MCS MCR
Expression
Input [ MCS ] [ MCR ]
Master control set / reset
Function
When the MCS input is ON, ordinary operation is performed. When the MCS input is OFF, the state of left power rail between MCS and MCR is turned OFF.
Execution condition
MCS input OFF ON Operation Sets OFF the left power rail until MCR Ordinary operation Output - -
Operand
No operand is required.
Example
When X000 is OFF, Y021 and Y022 are turned OFF regardless of the states of X001 and X002. Equivalent circuit
X000
Note
X001 Y021
· MCS and MCR must be used as a pair. · Nesting is not allowed.
X002
Y022
Basic Hardware and Function
133
6F3B0253
7. Instructions JCS JCR
Expression
Input [ JCS ] [ JCR ]
Jump control set / reset
Function
When the JCS input is ON, instructions between JCS and JCR are skipped (not executed). When the JCS input is OFF, ordinary operation is performed.
Execution condition
JCS input OFF ON Operation Ordinary operation Skips until JCR Output
Operand
No operand is required.
Example
When X000 is ON, the rung 2 circuit is skipped, therefore Y021 is not changed its state regardless of the X001 state. When X000 is OFF, Y021 is controlled by the X001 state.
Note
· JCS and JCR must be used as a pair. · Nesting is not allowed.
134
T1-16S User's Manual
6F3B0253
7. Instructions END
Expression
[ END ]
End
Function
Indicates the end of main program or sub-program. Instructions after the END instruction are not executed. At least one END instruction is necessary in a program.
Execution condition
Input Operation Output
Operand
No operand is required.
Example
Note
· For debugging purpose, 2 or more END instructions can be written in a program. · Instructions after END instruction are not executed. Those steps are, however, counted as used steps.
Basic Hardware and Function
135
6F3B0253
7. Instructions FUN 018
Expression
Input -[ A MOV B ]- Output
MOV
Data transfer
Function
When the input is ON, the data of A is stored in B.
Execution condition
Input OFF ON Operation No execution Execution Output OFF ON
Operand
Name X A Source B Destination Y Device R S T. XW YW RW SW T C D Constant Index I J K
Example 1 (constant to register)
When R010 is ON, a constant data (12345) is stored in D0100 and the output is turned ON.
Example 2 (register to register)
When X005 is ON, the data of SW30 is stored in RW45 and the output is turned ON. If SW30 is 500, the data 500 is stored in RW45.
Example 3 (index modification)
When R050 is changed from OFF to ON, the data of RW08 is stored in the index register I and the data of D(0000+I) is stored in YW10. If RW08 is 300, the data of D0300 is stored in YW10.
136
T1-16S User's Manual
6F3B0253
7. Instructions FUN 019
Expression
Input -[ A+1A MOV B+1B ]- Output
DMOV
Double-word data transfer
Function
When the input is ON, the double-word (32-bit) data of A+1A is stored in double-word register B+1B. The data range is -2147483648 to 2147483647.
Execution condition
Input OFF ON Operation No execution Execution Output OFF ON
Operand
Name X A Source B Destination Y Device R S T. XW YW RW SW T C D Constant Index I J K
Example
When R011 is ON, a double-word data of D0101D0100 is stored in RW17RW16 and the output is turned ON. [. . . ] block Special device Meaning and countermeasures A register/device which is not supported by the T1-16S is programmed. The timer or counter register is duplicated in the program. The subroutine number programmed with CALL or SUBR instruction is out of the range. (Error down) 0 to 255 Correct the program. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA T1-16S
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.