User manual TOSHIBA TCB-PCOS1E INSTALLATION MANUAL
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual TOSHIBA TCB-PCOS1E. We hope that this TOSHIBA TCB-PCOS1E user guide will be useful to you.
Lastmanuals help download the user guide TOSHIBA TCB-PCOS1E.
Manual abstract: user guide TOSHIBA TCB-PCOS1EINSTALLATION MANUAL
Detailed instructions for use are in the User's Guide.
[. . . ] · Incomplete installation causes an electric shock or a fire. Ask an authorized dealer or qualified installation professional to reinstall adapters. · Incomplete installation causes an electric shock or a fire. [. . . ] 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Name Wire(A) Wire(B) PCB Wire(C) Wire(D) Transformer Fixing plate(A) Cover Fixing plate(B) Spacer Clamp Screws(A) Screws(B) Binding band Holder Installation manual Q'ty 1 1 1 1 1 1 1 1 1 4 2 2 4 3 2 1 Q'ty to be used Work items RAV-SM56, 80 RAV-SM110, 140 Connect a timer (local procurement) to the CN300 of PCB 1 1 Connect a timer (local procurement) to the CN201 of PCB 1 1 1 1 Connect between the CN100 of the PCB and faston receptacle of terminal 1 1 block for power supply of the outdoor unit. Connect between the CN400 of the PCB and the PCB of the outdoor unit. 1 1 (SM56, SM80 : CN806 SM110, SM140 : CN804) Connect to the CN101 and CN102 of PCB 1 1 1 1 1 For attaching PCB 4 4 For fixing Wire clamp 2 For fixing Transformer 2 2 For fixing plate(A), Cover, and fixing plate(B) 2 4 Used suitably 3 3 2 1 1
2
13 2
<RAV-SM56, SM80>
10 4 3 6
(Transformer wire)
6
(Wire(D) only)
5 2
4 12 2
1 5 6
(Transformer wire)
7
13 2 8
<RAV-SM110, SM140>
(Transformer wire)
5 1 2
(Transformer wire)
6
6
(Wire(D) only)
5 3 9
6 13 2 10 11 2
12 2
3
4. Wiring diagram
An Outdoor unit is controlled as follows by connecting between a white and each line using Timer or Switch purchased locally. Local Supply PCB White White Common Night operation Black CN101 Black (Sound reduction by 5dB at cooling mode) Yellow CN300 Power peak-cut 0% Orange Yellow operation (stop) CN102 Red Orange Power peak-cut 50% operation Caution Red Power peak-cut 75% operation Don't connect two or more contacts of power peak-cut with CN201 CN100 white line at the same time. Compressor operation output Non-voltage ON/OFF output signal (Dry contact)
Transformer
Faston receptacle of terminal block for power supply of the outdoor unit
Wire(C)
(
)
CN400 Wire(D)
(to be purchased locally)
DC250V, 10mA to 1A DC24V, 10mA to 1A DC12V, 10mA to 1A
Inverter assembly PCB of the outdoor unit · SM56, 80 : CN806 · SM110, 140 : CN804
5. Parts installation method and assembly to the outdoor unit (SM56, SM80)
Installation method for the PCB of the outdoor unit
(1) Mount a Transformer to the rear side of the Fixing plate(A) using Screws(A) (2 pieces). (2) Install Spacers (4 pieces) and PCB to the front side of the Fixing plate(A). (3) Connect the Lead wires (2 types) of the Transformer to the CN101 and CN102 of the PCB. In addition, connect the Wire(C) (2-core) to CN100 and the Wire(D) (5-core) to CN400. To connect the Wire(A) and the Wire(B), refer to the Wiring diagram of installation method to connect the wires.
Transformer
Wire(C) (connected to the CN100)
Fixing plate(A)
Lead wires of the Transformer (connected to the CN101)
Screws(A) (2 pieces)
Extract the wires other than the wire(D) from this cut-away section Cover Screws(B) (2 pieces)
Wire(A) (connected to the CN300) Wire(B) (connected to the CN201)
Wire(D) (connected to the CN400)
Lead wires of the Transformer (connected to the CN102) PCB Spacer (4 pieces)
Extract the wire(D) from this cut-away section
CAUTION
Don't allow the wires to come into pinching with cover parts. Otherwise, the wires may be broken or heated or fire may occur.
(4) Close the cover to the Fixing plate(A) with Screws(B) (2 pieces). Pass the wires through the cut-away section of the cover and do not allow the wires to come into pinching.
4
Assembly to the Outdoor Unit
(1) Remove the Top plate. (3) Remove the Cover of packed valve and wiring lid. [. . . ] Pass the wires through the Clamp section of the Fixing plate(B) and do not allow the wires to come into pinching.
CAUTION
Don't allow the wires to come into pinching with cover parts. Otherwise, the wires may be broken or heated or fire may occur.
Wire(C) (connected to the CN100)
Lead wires of the Transformer (connected to the CN101)
Wire(A) (connected to the CN300) Clamp (Extract the wires other than the wire(D) from this clamp section) Fixing plate(B) PCB
Wire(B) (connected to the CN201) Wire(D) (connected to the CN400)
Clamp (Extract the wire(D) from this clamp section) Spacer (4 pieces)
Lead wires of the Transformer (connected to the CN102)
To connect the Wire(A) and the Wire(B), refer to the Wiring diagram of installation method to connect the wires.
5
Assembly to the Outdoor Unit
(1) Remove the Front cabinet. (2) Fix the Application Control Kit to the Inverter assembly with Screws(B) (2 pieces).
Install the Application Control Kit in the back of Inverter assembly.
Application Control Kit
Screws(B) (2 pieces)
(3) Connect the Wire (D) (5-core) to CN804 of the SUB PCB.
SUB PCB Connect the Wire(C) (2-core) to the faston receptacle of the terminal block for power supply. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA TCB-PCOS1E
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.