[. . . ] E05-412
TCS-NET Air-Conditioning Control System [Setting File Creation Software] User's Manual
Introduction
This is the User's Manual for the Setting File Creation Software (here after referred to as the "software") for the Air-conditioning Control System. · Setting File Creation Software Ver 2. 00 Revision 02 * This Software (Ver 2. 0 Rev 02) is not compatible with Ver 1. 0
· "Windows 2000" and "Windows XP" are trademarks or registered trademarks of Microsoft Corporation in the United States and other countries. · "Microsoft Excel" is a trademark or registered trademark of Microsoft Corporation in the United States and other countries. · All company names and product names appearing in this manual are the trademark or registered trademark of their respective holders. [. . . ] (2) Word in error code definition file Choose "0: Japanese, " "1: English2" or "2: Chinese (Simplified)" for the ERROR_CODE. DEF language output. Specify this when using two or more Touch Screen Controllers on a network. When only one Controller is used, leave this item as the default setting (1: Touch Screen Controller No. 1). (4) Intelligent Server Qty Specify the number of Intelligent Servers to be used. (5) Indoor unit total Qty Specify the number of indoor units to be controlled. For Digital Inverter/Super digital Inverter equipment, twin, triple and group control system is counted as one unit. (6) Daily report closing time (meter-read time) Specify daily report closing time in the "hh:mm" format. Default: 23:59
26
(7) Monthly report closing date Specify monthly report closing date. (8) Scheduled operation central setting Specify an operation mode for scheduled operation. The following 4 patterns can be selected.
Setting No central setting Setting No. 3 OFF (10 minutes after) OFF OFF + [ON/OFF] switching prohibition reset OFF + [ON/OFF] switching prohibition reset OFF + [ON/OFF] switching prohibition reset OFF (within 10 minutes) OFF OFF + [ON/OFF] switching prohibition reset OFF + [ON/OFF] switching prohibited OFF + [ON/OFF] switching prohibited ON ON ON + [ON/OFF] switching prohibition reset [ON/OFF] switching prohibition reset ON + [ON/OFF] switching prohibition reset
(9) Door-lock interlocking central setting Specify a door-lock interlocking operation. The following 4 patterns can be selected.
Setting No central setting Setting No. 3 Locking (OFF to ON) OFF OFF OFF + [ON/OFF] switching prohibited OFF Unlocking (ON to OFF) No action [ON/OFF] switching prohibition reset [ON/OFF] switching prohibition reset No action
(10) Energy monitoring Choose "1: Valid" or "0: Void" for whether to use energy monitoring. (11) Power meter pulse constant setting Choose "1: Valid" or "0: Void" for whether to input power meter pulse constant in "WHM_CH. DEF". (12) Stand-by power counting Specify "Outdoor refrigerant system heater capacity kW" calculation method in the "Indoor unit group definition" sheet. The following 3 methods can be selected. 1: Proportional sharing on indoor unit horse power codes : Calculated using the proportional sharing method. 2: Equal sharing on indoor units Qty : Calculated using the equal sharing method. 0: N/A : Stand-by power counting is always 0. (13) kW conversion coefficient (input prohibited) This coefficient is used when calculating outdoor refrigerant system heater capacity kW of indoor unit sw using the proportional sharing on indoor unit horse power codes. Do not change this value as it is fixed to 0. 75.
27
(14) Whole building display mode Specify a display unit when [Whole building] button is pressed. Choose "0: block, " "1: tenant, " "2: area, " or "3: R. C. [. . . ] Input "0F88" for Digital Inverter/Super Digital Inverter models. · "Outdoor unit object management No. " Input "FFFF". · "Domestic/overseas, " "Date of addition, " "Outdoor unit model name" and "Indoor unit model name" You need not input data for these items. When input of these items is completed, overwrite (save) the "unit_table. xls" file and close the window. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE TOSHIBA TCS-NET
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.